RS485 MODBUS Module 8AI

User Manual

Modbus  Dec 

Hex 

Register Name

Access

Description

40074

73

0x49 MIN alarm level 4

Read & Write

40075

74

0x4A MIN alarm level 5

Read & Write

40076

75

0x4B MIN alarm level 6

Read & Write

40077

76

0x4C MIN alarm level 7

Read & Write

40078

77

0x4D MIN alarm level 8

Read & Write

40079

78

0x4E Alarm settings 1

Read & Write

Alarm settings

0 – alarm due to the current analog signal value

1 – Remember the value of the alarm, until reset by the

master via Modbus

40080

79

0x4F Alarm settings 2

Read & Write

40081

80

0x50 Alarm settings 3

Read & Write

40082

81

0x51 Alarm settings 4

Read & Write

40083

82

0x52 Alarm settings 5

Read & Write

40084

83

0x53 Alarm settings 6

Read & Write

40085

84

0x54 Alarm settings 7

Read & Write

40086

85

0x55 Alarm settings 8

Read & Write

40087

86

0x56 Input 1 settings

Read & Write

Analog input mode:

0 – input disabled
1 – voltage 0V to 10V
2 – voltage -10V to 10V
3 – voltage 0V to 1V
4 – voltage -1V to 1V
5 – current 4mA to 20mA
6 – current 0mA to 20mA
7 – current -20mA to 20mA

To change the input mode you must to set jumper inside 
of module (see 5 – Module Connection and 6 - Selecting
the input mode
)

40088

87

0x57 Input 2 settings

Read & Write

40089

88

0x58 Input 3 settings

Read & Write

40090

89

0x59 Input 4 settings

Read & Write

40091

90

0x5A Input 5 settings

Read & Write

40092

91

0x5B Input 6 settings

Read & Write

40093

92

0x5C Input 7 settings

Read & Write

40094

93

0x5D Input 8 settings

Read & Write

40095

94

0x5E Output 1 settings

Read & Write

Alarm output settings

    0 – output is set by PLC
  +1 – value from input 1
  +2 – value from input 2
  +4 – value from input 3
  +8 – value from input 4
+16 – value from input 5
+32 – value from input 6
+64 – value from input 7
+128 – value from input 8

+256 – Output is set if value is greater than Alarm Value 

(register 40097 or 40098) („cooling”)

+512 – Output is set if value is less than Alarm Value 

( register 40097 or 40098) („heating”)

+1024 – The lowest value from selected inputs
+2048 – The greatest value from selected inputs
(if not select either of the two above options than is used
average value of selected inputs)

40096

95

0x5F Output 2 settings

Read & Write

40097

96

0x60 Alarm Value 1

Read & Write

Alarm value for outputs

40098

97

0x61 Alarm Value 2

Read & Write

40099

98

0x62 Alarm hysteresis 1

Read & Write

The hysteresis value for alarm outputs

40100

99

0x63 Alarm hysteresis 2

Read & Write

Expansion Module  – 8 analog inputs

User Manual

Version 1.5

12 / 15

Содержание 8AI

Страница 1: ...RS485 MODBUS Module 8AI Expansion Module 8 analog inputs Version 1 5 User Manual Manufactured for...

Страница 2: ...ithout incurring any liability for the purposes of commercial law This information does not release you from the obligation of own judgement and verification We reserve the right to change product spe...

Страница 3: ...te adapter The device has a set of 8 analog input measurements In addition the module is equipped with 2 configurable digital outputs This module is connected to the RS485 bus with twisted pair wire C...

Страница 4: ...4mA to 20mA resolution 3 75 A Current input 0mA to 20mA resolution 3 75 A Current input 20mA to 20mA resolution 3 75 A Measurement resolution 14 bits ADC processing time 16ms channel Digital outputs M...

Страница 5: ...shown below The module is mounted directly to the rail in the DIN industry standard Power connectors communication and IOs are at the bottom and top of the module USB connector configuration and indi...

Страница 6: ...terminated at both ends with a resistor across the line equal to its characteristic impedance Both ends must be terminated since the direction of propagation is bi directional In the case of an RS485...

Страница 7: ...rs Access to registers is via MODBUS RTU or MODBUS ASCII 3 5 1 Default settings You can restore the default configuration by the switch SW6 see 3 5 2 Restore the default configuration Baud rate 19200...

Страница 8: ...bits 8 8 data bits 40006 5 0x05 Response delay Time in ms 40007 6 0x06 Modbus Mode 0 RTU 1 ASCII 4 Indicators Indicator Description Power supply LED indicates that the module is correctly powered Comm...

Страница 9: ...RS485 MODBUS Module 8AI User Manual 5 Module Connection Expansion Module 8 analog inputs User Manual Version 1 5 9 15...

Страница 10: ...odule as shown below Jumper Description off Voltage measurement shorted Current measurement 7 Switches Switch Function Description 1 Module address 1 Setting module address from 0 to 31 2 Module addre...

Страница 11: ...uts Read Write Alarms state bit 8 and 9 alarm outputs 30053 52 0x34 Analog 1 Read Value of analog input in mV for voltage inputs in A for current inputs 30054 53 0x35 Analog 2 Read 30055 54 0x36 Analo...

Страница 12: ...ion and 6 Selecting the input mode 40088 87 0x57 Input 2 settings Read Write 40089 88 0x58 Input 3 settings Read Write 40090 89 0x59 Input 4 settings Read Write 40091 90 0x5A Input 5 settings Read Wri...

Страница 13: ...ut is connected 807 806 0x326 Input 7 Read Set when the input is connected 808 807 0x327 Input 8 Read Set when the input is connected 817 816 0x330 Alarm 1 Read Alarm state 1 818 817 0x331 Alarm 2 Rea...