7.4 Auxiliary output undelayed flashing (RLU)
(S1 = „ON“, S3 = „OFF“ or S4 = „ON“, S6 = „OFF“)
With S1, flashing of the auxiliary output can be activated in synch with the LEDs (factory setting of S1 or
S4 = „Off“).
Safety output (symbolic)
Auxiliary output (symbolic)
7.5 Auxiliary output delayed (RL)
(S3 = „ON“, S1 = „OFF“ or S6 = „ON“, S4 = „OFF“)
In this operating mode, the respective auxiliary output is activated with a delay of approx. 0.5 second and
then remains active for max. 3 seconds if an error is signalled. The auxiliary output can be toggled between
normally closed contact and normally open contact with S2, whereby the output is always inactive while in
a power-free state.
S1 or S4 (ELMON rail 38-726 only) must be in the „Off“ switch position (factory setting); otherwise, the
auxiliary output is permanently inactive.
Safety output (symbolic)
Auxiliary output (symbolic)
0,5 s 3 s
8. Mechanical mounting
The switching unit must be professionally mounted:
- In a dust- and moisture-protected switching cabinet or housing.
- Installation in a Pollution Degree 2 environment.
- With a protection class of at least IP54.
- On a 35 mm DIN mounting rail acc. to EN 50 022.
The switching unit must not be mounted in the immediate vicinity of strong sources of heat.
The switching unit may be mounted in any orientation.