Fitting instructions
ASKO
HEAT‐
F
Flange heater Ø 180 mm
ASKO
HEAT‐
F
_
180_2-9_en
MVGASV_120101_en_V3
www.askoma.com
Page 4
E l e c t r i c a l c o n n e c t i o n
The device is intended for fixed connec on only and may be connected only to fixed cables. Select a
cable cross-sec on suitable for the power ra ng of the device. All poles of the device must be able to
be disconnected from the mains by means of an at least 3 mm isola ng distance. The PE wire must be
100 mm longer than the other conductors.
I n t h e e v e n t o f t h e f o l l o w i n g t h e g u a r a n t e e i s v o i d :
- Not complying with this paperwork „Fi ng instruc ons, user manual and service“
- Not complying with the boiler manufacturer's fi ng instruc ons
- Technical modifica ons, repairs or tampering with the device (including exchanging the thermostat)
- Applica ons for which the device was not designed
- Incorrect opera on and maintenance
- Not complying with direc ve VDI 2035
A p p l i c a b l e s t a n d a r d s
Safety:
EN60335-1 / -2-21 / -2-73
EMC:
EN55014-1 / -2
CEM:
EN62233
IP Code:
EN60529