11
The inverter will indicate high and low DC voltage conditions as follows:
Model
DC Input over
voltage shut-down
DC Input over
voltage alarm
DC Input under
voltage alarm
DC Input under
voltage shut-down
YK-PIC30122KVA
YK-PIC30122KVAE
16.0VDC
15.5VDC
10.5VDC
10.0VDC
YK-PIC15242KVA
YK-PIC15242KVAE
32.0VDC
31.0VDC
21.0VDC
20.0VDC
YK-PIC08482KVA
YK-PIC08482KVAE
62.0VDC
61.0VDC
43.0VDC
42.0VDC
2-7-2 Output Voltage indicator
LED displays light on VAC as show as output voltage value.
2-7-3 Output Current indicator
LED displays light on AMP as show as output current value.
2-7-4 Output Watts indicator
LED displays light on Watts as show as output watts value.
2-7-5 Input DC Voltage indicator
LED displays light on VDC as show as input DC voltage value.
2-7-6 Temperature indicator
LED displays light on TEMP as show as internal operating temperature value.
2-7-7 Output Frequency AC indicator
LED displays light on Hz as show as output frequency value
Please have the accuracy of 6 functions of display, as below:
Functions
VAC
AMP
WATT
VDC
TEMP Frequency
Ranges
100-120
VAC
200-240
VAC
0-40A
0-2KW 10-16 VDC 20-32 VDC 42-62 VDC 0-120
°
C 50Hz 60Hz
Accuracy
±
1%
±
1%
1%
±
0.5A
±
3%
±
2%
±
2%
±
2%
±
1%
±
0.01
±
0.01