KM11 PRESSURE TRANSMITTER  
INSTRUCTION SHEET

 

 

  

 

  

WARNING! READ 

BEFORE  INSTALLATION 

 

The ATEX approved pressure 
transmitter of Ashcroft KM11 family 
are designed to sense pressure in 
facilities with gaseous or liquid 
media. They are usable in zone 1. 
 
Transmitters are affected with the 

approval number

  

TÜV06ATEX2975  
 

and markings 

II 2G Ex ia IIC T4 Gb 
-

40°C ≤ Ta ≤ 85°C 

 

Label

 

 

 
 

CONDITIONS GOVERNING THE 
USE OF THE PRODUCT 

 

General directions

  

to be complied with at all times for 
correct and safe use of the 
electronic pressure transmitter: 

  Please keep within the limit 

values given in the specification 
for such items as pressure, force, 
torque and temperature. 

  Give due consideration to the 

prevailing ambient conditions 
(temperature, atmospheric 
humidity, atmospheric pressure, 
etc.) 

  Observe the applicable safety 

regulations laid down by the 
regulatory bodies in the country of 
use. 

  Use the product only in its original 

conditions. Do not carry out any 
unauthorized modifications. 

  Remove all items providing 

protection in transit such as foils, 
caps or cartons. 

 

OPERATING CONDITIONS

 

  Type testing does not apply to all 

ambient conditions without 
limitations. The user is 
responsible for verifying that the 
plug-and-socket connection 
complies with the specified rules 
and regulations, or whether it may 
be used for specialized purposes 
other than those intended by use. 

  The values given in the technical 

data for overpressure safety 
relate to the hydraulic or 
pneumatic part of the pressure 
transmitter. 

  The EN 60079-0:2012 and 

EN 60079-11:2012 standards 
were applied. 

  Ambient temperature range 

-40 °C up to +85 °C 

  Medium temperature range 

-40 °C up to +85 °C 

  Safety related maximum values of 

electrical connection: 
U

i

 

30 V DC 

 

I

i

 

50 mA  

C

i

 

5 nF 

L

i

 

negligible 

Consider for connected cable 
C

i

 = 300 pF/m and L

i

 = 1 µH/m 

 

INSTALLATION 
Mechanical / pneumatic / 
hydraulic: 

  Screw the electronic pressure 

transmitter into the pressure 
connection provided using an 
open-jaw spanner of 22 AF size 
(as per DIN 894 or similar), with a 
tightening torque of approx. 
25 Nm. 

  To seal the system, use a 

standard copper seal with the 
appropriate dimensions. 

 

Electrical: 

  All wiring should conform to local 

codes and must be carried out by 
authorized personal only. Keep 
high and low voltage wiring 
separated. For applications in 
critical industrial environment use 
special cables. 

  Observe without fail the 

connecting information – labeled 
on the transmitter or laid down in 
the operating instructions – while 

connecting the pressure 
transmitter. 

  Ensure that the cables routed 

without crushing. 

  Electricity supply and wirings 

must be suitable for the demands 
of the hazardous area. 

  The electricity supply of the 

transmitter must occur according 
to the regulations for intrinsic 
circuits. A security (e.g., glaze) 
protection is recommended. 

  When allocation is valid with 

cable connection: 
4-wire ventilated or unventilated 
cable 
red   Loop +   
black  Loop –  
white  (not connected)  
 
 

Indication

 

Pressure is balanced by a micro 
filter (in level sensors by a capillary 
in the cable) between the trans-
mitter and the ambient 
environment. This allows explosive 
mixtures from the ambient 
environment to intrude into the 
transmitter or it is possible that 
mixtures accumulating inside the 
transmitter due to diffusion escape 
from the housing. 
 

DIMOUNTING 

  When disassembling the pressure 

system, it must be depressurized. 

  Please observe applicable safety 

regulations when removing the 
pressure transmitter. 

 

DISPOSAL

 

  Please help to protect the 

environment and dispose of or 
recycle the devices and 
components used in accordance 
with the applicable regulations. 

 
 

 