Ashcroft AUF Скачать руководство пользователя страница 4

 

6.3  Range (value to be displayed at 20 mA) 

 

Press B key until E P 2 0 is displayed 

=>A+B menu item to set - 0 0 0  

=>B or A for up and down 6 0.0 0 (60 psig)  

=>A+B to confirm setting and return to menu item - E P – 

 

6.4  Attenuation  

 

Press B key until F I L t is displayed  

=>A+B menu item to set 0 0 0.3 (Min.=0.3 sec.;Max.=20.0 sec.)  

=>B or A for up or down - - 1.5 (1.5 sec.)  

=>A+B to confirm setting and return to menu item F I L t  

 

6.5  Range Exceeded (displayed if below 4 mA or above 20 mA)  

 

Display: “HI”=>range exceeded or “L0”=>below range  

Press B key until H I L 0 is displayed 

=>A+B menu item for setting: - 0 F F display inactive  

=>B or A for up or down: - 0 n - display active  

=>A+B to confirm setting and return to menu item H I L 0  

Report - h I - = measuring range exceeded, - L 0 - = below measuring range  

Please note: If H I L 0 display is inactive, measuring range exceeded (-1999 to 9999) is indicated by     

“E r 0 6” 

  

6.6  Operating Position (Option)  

 

Press B until - S P t is displayed 

=>A+B menu item for setting - 0.0 0  

=>B or A for up or down: 2 0.0 0 (20 psig)  

=>A+B to confirm setting and return to menu item - S P t  

Please note: Standard hysteresis is the set point minus 3 digits 

Upon customer request, the hysteresis is adjustable at the plant as per request 

 

 
 
 
 
 
 

Rev. Jan. 2002  