Asentria SiteBoss 571 UserManual
Page 94
Event / Normal Class
Set the class for the event. When this option is selected, a list of the classes previously defined in the
is displayed. Select one to be assigned to this event. The default is Info.
Sensor Unresponsive Settings
This is used to configure the actions the SiteBoss should take if an EventSensor becomes unresponsive.
SiteBoss 571 - Sensor Unresponsive Menu
A) Sensor Unresponsive Timeout [30]
B) Sensor Unresponsive Actions []
C) Sensor Unresponsive Trap Number [50]
D) Sensor Unresponsive Class [Info]
Sensor Unresponsive Timeout
sets the number of seconds (10 - 65535) to wait before declaring a non-
communicative EventSensor unresponsive. Default setting is 30.
Sensor Unresponsive Actions
displays the Action List, a menu where the action string for the event is
configured. This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more
actions have been configured. Refer to
Action List
in the Features chapter for more information.
Sensor Unresponsive Trap Number
sets the number to be sent with any SNMP traps for this event. Default is
50, but trap number can also be set in the range of 1000
– 1199 as needed.
Sensor Unresponsive Class
sets the class for the alarm. When this option is selected, a list of the classes
previously defined in the
is displayed, from which you can select one to be assigned to this event.
Load Shedding Settings
The purpose of the load shedding feature is to allow individual configuration of switch, relay and/or power outputs
to selectively shut off power to connected equipment after mains power is lost.
The load shedding feature works only in conjunction with a supported rectifier. The supported rectifiers are Eltek-
Valere NIC2000, Eltek-Valere BC1000, Eltek-Valere BC2000 and Delta CSU503.
For load shedding to work properly, the rectifier and network must be configured so that SNMP traps are received
by the SiteBoss when mains power is lost or restored, and so that the SiteBoss can retrieve the battery voltage via
SNMP requests while mains power is lost. If communication with the rectifier is interrupted for any reason, the load
shedding functionality may not work correctly.
This menu covers the global settings for the Load Shedding functions within the SiteBoss. Each Individual power
output will have its own individual load shedding menu to configure load shedding options individually.
See the
on the Asentria Product Information Portal or contact
SiteBoss 571 - Load Shedding Settings
A) Enable [OFF]
B) Rectifier Controller [Eltek-Valere NIC2001]
C) Rectifier IP Address [0.0.0.0]
D) Rectifier SNMP Community Name [public]
E) Event Enable [OFF]
F) Event Actions []
G) Event Trap Number [525]
H) Event Class [Info]
Enable
This is an ON/OFF toggle to set whether load shedding is enabled or disabled. The default is OFF.