Asentria SiteBoss 530 User Manual
6
Remote Access
The S530 can provide an administrator transparent access to devices connected to the serial ports of the unit via
passthrough connections or through the login menu in the web interface, Telnet, and modem connections. This
sort of access can be used to configure, maintain, or manipulate devices that would normally have no remote
access.
Serial Monitoring (Data Events)
The S530 can be used to monitor incoming data for user-defined strings and then report the event via several
avenues. The S530 allows for up to 1000 different data events. Each data event contains independent actions,
counters, and other unique settings. Data events triggered within the S530 can be logged to an Event Log. This
file can be viewed through the Event Log section of the setup menu, via the
TYPE EVENTS
command, FTP, or
the web interface.
Event Notification
Actions generated or detected within the S530 can be delivered through any of the following means:
●
Modem
callout
●
Dialup
pager
●
Relays (if configured with optional relay Expansion Card)
●
SNMP
trap
●
SMS
Messages
●
●
Asentria Alarms
Audit Log
The S530 has the capability to log many types of administrative events, from serial port handshaking alarms to
login attempts. These Audit Log entries are stored in a file and can be viewed through the Audit Log section of
the Setup menu, via the
TYPE AUDIT
command, FTP, or the web interface.
Integration with SitePath
Using the S530 in conjunction with Asentria’s SitePath Remote Management System, you can create secure and
controlled IP access to remote servers and appliances co-located on the same remote network as the S530.
SitePath uses an integrated SSL or IPSEC VPN implementation which simplifies otherwise complex VPN setup
down to a few easy steps, allowing users to access remote devices via the SitePath VPN Gateway. The S530
plus SitePath provide IP routing to authorized remote network addresses, and prevents unauthorized access to
any other addresses on the remote LAN.
Parts Identification
Features and Accessories
Standard Equipment
The base S530 comes with the following standard on-board equipment:
•
AC or DC Power Input
•
32MB logging database for CDR or other text records
•
2 – RJ45 DTE serial I/O ports
•
1 – 9 pin Mini DIN SensorJack port for connection of Type2 EventSensors
•
2 – 10/100Mb Ethernet interfaces
•
1 – MMC memory I/O slot
•
2 or 6 – Expansion Card slots
•
Internal lithium coin-cell type battery backup*/**
*
Battery backup preserves clock operation when power is not present. Data records and settings are stored in non-
volatile memory and therefore do not require battery backup.
**
CAUTION: THERE IS A RISK OF EXPLOSION IF THE BATTERY IS REPLACED BY AN INCORRECT
TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
The instructions are that
lithium batteries can be recycled, and you should contact a recycling organization in your area for details.
In addition to the above components, the standard unit is shipped the following accessories:
•
This product manual on the Documentation and Software CD
•
RJ45 M-M unshielded serial cable and RJ45/DB9 straight thru adapter for each serial port ordered
•
RJ45 Ethernet cable for each Ethernet port
•
Power supply adapter (for AC units), or wiring harness and Molex plug (for DC units)
Содержание SiteBoss 530
Страница 6: ......