11
LOAD CAPACITY (KG/
DRUM PLATFORM)
IO90.195.120.K3.WDC
max.
75 kg
max.
50 kg
max.
180 kg
IO90.195.060.K9.WDC
IO90.195.060.L8.WDC
IO90.078.059.057.U9.S
max.
25 kg
max.
50 kg
max.
25 kg
drawer
Second level drawer
CAUTION:
The position of the shelves / 2nd level drawer and socket strips cannot be changed.
Total power rating of the power socket strips
Standard: single-phase, 230 V
EU
CH
UK
FR
16 A
10 A
13 A
16 A
3,68 kW
2,3 kW
2,99 kW
3,68 kW
Optional: 3-phase, 400 V (accessories article 38038)
EU
CH
UK
FR
3 x 16 A
3 x 10 A
3 x 13 A
3 x 16 A
11,04 kW
6,9 kW
8,97 kW
11,04 kW
ATTENTION:
- The load on the system is to be distributed as evenly as possible over the power socket strips!
- The individual power socket strip may not be loaded with more than 3.68 kW!
- The necessary fuse protection is to be provided by the customer!
6. STORAGE
•
ATTENTION:
Never store obviously damaged lithium-ion batteries inside buildings.
Dispose of them without delay in disposal containers that are provided outside the building and approved
for transport.
6.1. NOTES ON STORAGE AND CHARGING
Storage
• It is recommended to store new and used lithium-ion batteries separately (each on a different storage level)
in the safety storage cabinet.
IO90.195.120.K2.WDC, IO90.195.120.K3.WDC - Occupation of the storage levels
• Grid shelves may be covered only up to 60% by battery chargers and batteries in order to ensure trouble-free
operation of the fire suppression system and sufficient air circulation (see point 6.3).
It is not permitted to occupy the complete area of the grid shelves.