AC25/30QTP-1 and -3 Operations Manual.... 47
TRANSFER ON OVERLOAD CONTROL
Feature: Disabled, Select Genset: 1
Enable Disable Forward Back Exit
7.3
LOAD MANAGEMENT OPERATION, cont.
7.3.4 Automatic Transfer to Generator
, Single or Master Converters (Seamless Transfer
installed)
Upon Shore Alarm, the Automatic Transfer to Generator feature may be used to perform a
Seamless Transfer to a pre-selected generator. This implies connection and setting of the
Generator Autostart Control feature (needed to signal a generator to start and hold the set warm-
up time before transferring). The transfer is not initiated until Voltage Droop has occurred as the
load savings afforded may have taken the converter out of Shore Cord Alarm.
From the front panel, press the
SHORE POWER
+
F2
buttons, and then Transfer (
F3
) to access
the following screen:
Press the
F1
or
F2
buttons to adjust the Feature or Select Genset settings; Forward (
F3
) to
advance the cursor to the Select Genset setting; Back (
F4
) to return the cursor to the Feature
setting, and Exit (
F5
) to save the settings and exit the screen. When the cursor is on the Feature
setting, the
F1
/
F2
buttons will read Enable/Disable. When the cursor is on the Select Genset
setting, the
F1
/
F2
buttons will read More/Less.
Default Range
Feature DISABLED
DISABLED/ENABLED
Genset
1 - 4