AC112Q-3, AC125Q-3, AC150Q-3, and AC165Q-3 Operations Manual.... 19
5.2
ELECTRICAL INSTALLATION
This procedure assumes the physical installation of the converter has been completed.
It is the installer’s responsibility to provide input service over-current protection and disconnect
means.
It is recommended that connection be made to the distribution bus through a manually operated
disconnect device such as a molded case switch or circuit breaker (rated for the total system
amperage) to ease disconnection and provide a safe servicing environment in the event of converter
failure.
Follow the table below when considering shore power input cabling.
Table 7: Maximum Input Current under Low-Line Conditions
Model
AC112Q-3
AC125Q-3
AC150Q-3
AC165Q-3
Input Current @
330Vrms (L-L)
180 Arms
200 Arms
240 Arms
264 Arms
MAXIMUM OUTPUT CURRENTS: Refer to Table 1
All power wiring requires the removal of the front panel and the cable access cover (cabinet
bottom). Drill or punch appropriate holes for the selected strain reliefs. Re-install the front panel
using the removed hardware. Place the disconnect switch in the OFF position.