AC112Q-3, AC125Q-3, AC150Q-3, and AC165Q-3 Operations Manual.... 47
7.3
LOAD MANAGEMENT OPERATION, cont.
7.3.5 Quick Setup of Shore Cord Alarm
, Single, Master, or Slave Converters
1. Turn on the red Disconnect switch of both converters and wait 15-20 seconds for initialization.
2. Press the
SHORE POWER
+
F2
buttons on both converters.
3. Press the Cursor (
F4
) button to advance to the ALARM AT % setting.
4. Set the converter ALARM AT % using the More/Less (
F1
/
F2
) buttons.
5. Press the Cursor (
F4
) button to advance to the ALARM enable setting.
6. Set the converter ALARM enable using the Enable/Disable (
F1
/
F2
) buttons.
7. Press the Exit (
F5
) button to save the settings and exit.
8. Turn on the converters and place online as usual. Alarm will occur when loading reaches the
ALARM AT % setting.
Quick Setup of Load Sharing
, paralleled Converters
1. Turn on the red Disconnect switch of both converters and wait 15-20 seconds for initialization.
2. Press the
SHORE POWER
+
F2
buttons on both converters.
3. Press CORD (
F1
) on both converters.
4. Set the Master’s SHORE CORD AMPACITY in amps using the More/Less (
F1
/
F2
) buttons.
5. Set the Slave’s MASTER CAPACITY in kVA (read from the Master’s Shore Cord Setup
screen) using the More/Less (
F1
/
F2
) buttons.
6. Advance to the Slave’s SLAVE CORD AMPACITY using the Forward (
F3
) button and set the
amps using the More/Less (
F1
/
F2
) buttons.
7. Press the Exit (
F5
) button twice on both converters to save the settings and exit.
8. Turn on the converters and place online as usual, and verify an imbalanced share in Load Level
% or individual Converter Output Amps at a ratio approximate to that ratio between the converter’s
programmed capacities.