    IS-PM824

Instructions for Installing PM-824  

Remote snow/ice sensor

The PM-824 is a 24 volt, self contained snow and ice detector. Each 

PM-824 can be set to operate within a range of 22-28 V. The integrated 

snow sensor is heated to allow for snow, ice, or freezing rain to melt, 

allowing proper detection of environmental conditions.

Installation

The PM-824 control can be mounted in any location as long as the  
moisture grid sensor is installed in a location that exposes the moisture 
grid to a clear view of the sky and any precipitation. 

Note: the moisture 

grid should not be mounted directly under eaves, overhangs, or  
other obstructions that can block precipitation from reaching the 
moisture grid. 

Do not install the control or sensor close to the ground, or any other  
location, that can cause the unit to be buried in snow. 

Mount the PM-824 moisture grid outdoors, away from furnace vents, dryer 
vents, and other sources of heat. The PM-824 control can be mounted to a 
free-standing conduit or by using the mounting holes in each corner of the 
enclosure. Do not drill holes in the enclosure.

Wire the controller in accordance to the provided schematics.

Operation

Before installing and wiring the PM-824 sensor, it is 

important to set all power and control settings prior to 

wiring or mounting.
1.   Set the Temp Adjust control for desired melting  

conditions. Precipitation below this temperature is 

assumed to be snow, above rain. Control comes with 

the Temp Adjust dial set to 39°F.

2.   Set the Delay (DEL) time for 30–90 minutes when the 

LD (Long Delay - see #3) switch is set to OFF, or 2 – 6 

hours when LD is ON.  

 

The Delay function will allow the snowmelt system to 

run for the set time frame after moisture is no longer 

detected (once snowfall has stopped). This is to help 

prevent "black ice" from forming. 

3.   Determine how the sensor operates by setting the 

toggles located at S1. 

Snow:

   On – the control will operate when precipitation is detected below 

the Temp Adjust setting. 

Recommended: ON

Rain:

     On – the control will operate when precipitation is detected above 

the Temp Adjust setting. 

Required: OFF

DEL:

      On – the control will operate with a Delay Off time. If this function 

is set to Off, the control will operate with a 2 minute delay to 

prevent short-cycling of external components. 

Recommended: ON

LTC:

     On – the control will operate in Low Temperature Cutoff mode, 

preventing operation when Ambient Temperatures (AT) fall below 

15°F. 

Recommended: ON

LD:

      On - the control will operate with a Delay (DEL) time (see #2 

above) of 2 - 6 hours.  If this function is Off, the control will operate 

with a 30 - 90 minute Delay time. 

Recommend-

ed: OFF

4.   The control monitors the moisture sensor once every second for the 

presence of moisture. Setting the sensor sensitivity dial to "Less" 

requires a full four (4) minutes of detection before the unit activates 

the snowmelt system. Set to "More" requires only three (3) seconds 

of detection. Adjust this setting to avoid nuisance triggering due to 

condensation, blowing snow, or high winds, or flurry conditions.

Power must be cycled for switch changes to take effect.
Manual Override Switch

An override switch is mounted on the side for testing and special  

operational requirements. Placing the switch in the "Automatic" position 

will allow the sensor to operate normally. "Manual On" will activate the 

control and will stay activated for a maximum of 40 hours before returning 

to "Automatic" mode. The "Stand-by/Reset" position will clear any current 

snowmelt call or delay activity.
If the Manual Override Switch is moved to Manual On for less than  

2 seconds and then back to Automatic the sensor will execute one delay  

off cycle. This can be used to clear frost, hail, drifting snow, or other  

conditions. Stand-by/Reset will clear this setting.

FMO

30M 

(2H)

60M 

(4H)

90M

(6H)

FMO

30M 

(2H)

60M 

(4H)

90M

(6H)

FMO

30M 

(2H)

60M 

(4H)

90M

(6H)

FMO

30M 

(2H)

60M 

(4H)

90M

(6H)

!

 

WARNING: General Safety Instructions

1.  

THIS UNIT SHOULD BE INSTALLED ONLY BY  

QUALIFIED PERSONNEL!

2.  Disconnect all power from the control, or any associated equipment, 

before opening the front cover plate.

3. Limit input voltage to 22-28 VAC/VDC
4.  To avoid fire hazard, replace fuse 

only 

with 2 Amp 32 V or 250 V 3AG 

fast acting fuse. 

5.  Do not drill holes through the electrical enclosure for mounting.  

Mount the control to a free-standing conduit or via the pre-determined 

mounting holes.

6. Ensure front cover gasket is properly installed when replacing cover.





�

























ENCLOSURE TYPE 3R









PM-824 provides integrated air and moisture detection within a rainproof 

and ice-resistant enclosure. The moisture grid can be locate up to 10 ft 

away from the main control.

Air Temperature Sensor

Wiring Access

Control Switch

Moisture Grid