Parameter
Description
Range
Default
27
r.dh
Humidity intervention differential (Hysteresis)
0.0 ÷ 30.0°C/°F
5.0
28
r.h1
Humidity Output (
ot
) enable time for H. probe error
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
1.00
29
r.h2
Humidity Output (
ot
) disable time for H. probe error
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
30
r.ud
Humidity Output (
rh
) operating mode
u Humidifies;
d Dehumidifies;
nr
Neutral zone (
rh
= Dehumidifies,
hu
= Humidifies)
u
31
P.t1
ot
temperature control output activation delay
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s. x 10)
oF
32
P.t2
ot
temperature control output activation delay after
ot
switch OFF
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
33
P.od
Outputs activation delay at power ON
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
34
A.yt
Temperature alarms type
1
Absolute with label (
Hit
-
Lot
) display;
2
Relative with label (
Hit
-
Lot
) display;
3
Absolute with no label display;
4
Relative with no label display.
1
35
A.Ht
High temperature Alarm threshold
oF/-99.9 ÷ 999 °C/°F
oF
36
A.Lt
Low temperature Alarm threshold
oF/-99.9 ÷ 999 °C/°F
oF
37
A.dt
Temperature alarm differential
A.Ht
and
A.Lt
0.0 ÷ 30.0°C/°F
1.0
38
A.tt
Temperature alarm delay
A.Ht
and
A.Lt
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
39
A.yh
Humidity alarms type
1
Absolute with label (
Hih
-
Loh
) display;
2
Relative with label (
Hih
-
Loh
) display;
3
Absolute with no label display;
4
Relative with no label display.
1
40
A.Hh
High humidity Alarm threshold
oF/-99.9 ÷ 100 RH%
oF
41
A.Lh
Low humidity Alarm threshold
oF/-99.9 ÷ 100 RH%
oF
42
A.dh
Humidity alarm differential
A.Hh
and
A.Lh
0.0 ÷ 30.0 RH%
1.0
43
A.th
Humidity alarm delay
A.Hh
and
A.Lh
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
44
A.PA
Temperature and Hunidity Alarms delay at power ON
oF/0.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10)
2.00
45
A.oA
Alarm delay with door open
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
3.00
46
o.o1
OUT1 function
oF
No Function;
ot
Temperature control (Cooling if
r.HC
=
C
,
CP
,
nr
;
Heating if
r.HC
=
H
o
HP
);
rh
Humidity control (Dehumidification if
r.ud
=
d
,
nr
;
Humidification if
r.ud
=
u
);
HE
Heating (with
r.HC
=
nr
);
hu
Humidification (with
r.ud
=
nr
);
Au Auxiliary;
At/-t Acknowledgeable alarm;
AL/-L Not Acknowledgeable alarm;
on
Output active when the instrument is ON;
L1 Light
ot
47
o.o2
OUT2 function
rh
48
o.o3
OUT3 function
Au
49
o.bu
Buzzer function mode
oF Disabled;
1
Active alarms only;
2
Key pressed only;
3
Active alarms and key pressed.
3
50
o.Fo
Auxiliary output operating mode
oF No function;
1
Manual activation by key or digital input;
2
Independent twin timer;
3
Twin timer enabled only when the temperature
control is disabled (when Temp. contr. enabled the
output is always ON).
2
51
o.tn
ON time relating to the auxiliary output
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
52
o.tF
OFF time relating to the auxiliary output
oF/0.01 ÷ 9.59 (min.s o h.min) ÷ 99.5 (min.s o h.min x 10) oF
53
o.tu
Unità di misura parametro
o.tF
H h.min;
n min.s.
n
54
t.UF
key operating mode
oF No function;
1
Auxiliary output command;
2
Switch on/off (Stand-by)
3
Start Autotuning;
4
Light ON/OFF (
L1
Output).
oF
55
t.Fb
key operating mode
oF
56
t.Lo
Keyboard lock function delay
oF/0.01 ÷ 9.59 (min.s) ÷ 30.0 (min.s x 10)
oF
57
t.Ed
key Fast Set Point change procedure;
Setp Point visibility
oF None;
1
SPt
;
2
SPh
;
3
SPt
and
SPh
.
3
58
t.PP
Access Password to parameter functions
oF ÷ 999
oF
59
t.Ad
MODBUS address (serial communication)
0 ÷ 255
1