Ascon Tecnologic - TRH-MINI - ENGINEERING MANUAL - PAG. 2

Electrical connections

Carry out the electrical wiring by connecting only one wire to each 

terminal and according to the following diagrams:

General notes about wiring

1. 

Do not run input wires together with power cables.

2. 

When a shielded cable is used, it should be connected at one 

point only.

Power supply

Power supply: 8... 24 DC
Range: -20... +80°C, 0... 100% RH

TRH-MINI

GND VDC  B      A

+

8... 24 VDC

Serial Interface

Power supply: 8... 24 DC
Range: -20... +80°C, 0... 100% RH

TRH-MINI

GND VDC  B      A

B
A

RS-485

B

A

Controller

A

B

A

B

A

B

120

n

th

TRH

2

nd

TRH

1

st

TRH

Notes: 1. 

RS-485 interface allows to connect up to 30 devices 

with one remote master unit.

2. 

The cable length must not exceed 1.5 km at 9600 baud.

TECHNICAL CHARACTERISTICS

Tecnical specifications

Characteristic

Relative Humidity

Temperature

Measuring range

0... 100%

-20... +80

Resolution

0.1% RH

0.1°C

Accuracy

±3% RH

±0.5°C

Note: 

When the sensor is external the temperature range is  

-40… +120°C

Electrical specifications

Characteristic

Value

Supply voltage

8... 24 VDC

Power consumption

< 30 mA

General specifications

Characteristic

Value

External dimensions

45 x 65 x 28 (L x H x D)

Mounting

DIN Rail
2 screws Ø3 mm max.

Weight

About 60 g

Work area

10... 20 m

2

, with air circulation

Installation position

Horizontal or vertical

Working temperature

-20... 70°C

Ambient humidity

5... 95% (with no condensation)

Case material

PC + ABS

Serial communications

Characteristic

Value

Interface type

Isolated RS485

Voltage levels

According to EIA standard

Protocol type

MODBUS RTU

Byte format

8 bit with no parity

Stop bit

1 (one)

Baud rate

Programmable between 1200... 38400 baud

Address

Programmable between 1... 247

HOW TO ORDER

TRH-MINI

 Relative Humidity and Temperature sensor.

RS485 COMMUNICATIONS

Code system

8 bit binary, hexadecimal 0... F, each word (8 bit) contains 2 

hexadecimal characters.

Modbus RTU bits per byte in the protocol

1

  Start bit;

8

  Data bits (the less important bit must be sent as first);

-

  No parity;

1

  Stop bit.

Error detection domain

CRC-16 (Ciclic Redundacy Check), the lowest is in front, the 

highest byte behind.

Communication speed

1200, 2400, 4800, 9600, 19200 baud per second.
The baud rate and the instrument address must be set using the 

communications protocol.