background image

3

Customer Care Center, 1-800-898-1879, www.askona.com

Built-in

4-1/2" 

8-3/4" 

222 mm

115 mm

29-7/8"

758 mm

ASKO dryers can be installed beneath a 
cabinet or worktop with a minimum height of 
34” (864 mm). There must be a gap of about 
1/2” (12 mm) all around the machine, including 
between the rear side of the machine and the 
back wall. The opening width must be at least 
24-1/2” (622 mm).

NOTE!

•  The height adjustment for the dryer is 33-

1/2” to 34-1/2” (850 mm to 876 mm). Do 
not raise it higher than 34-1/2” (876 mm). 
Hole measurements are from center of hole.

Install in a closet

ASKO’s front panel controls make it possible to 
install the washers and dryers in a closet. Make 
sure there is a ½” (12 mm) minimum clearance 
between units and cabinet or wall. To ensure 
proper ventilation, we recommend louvered 
doors.
Otherwise there must be ventilation openings 
in the door. See illustration for minimum 
ventilation openings:

NOTE!

•  Ensure the dryer door can be opened 

without hindrance after installation.

NOTE!

•  The cool air intake panel at the front of 

the dryer must not be blocked or covered. 
Doing so could cause a fault.

Air exhaust

NOTE!

The tumble dryer must only be operated when 
it is correctly fi tted with exhaust duct.

Connecting the exhaust duct to the dryer

NOTE!

You will need to purchase a UL-CSA-approved 
4” ridged metal exhaust duct. The dryer is 
delivered with the stub pipe attached to the 
rear exhaust outlet, though the exhaust duct 
can be attached to either the left or the right 
exhaust outlet.

Vent

T-tube

Rear Exhaust 
Outlet

Side Exhaost 
Outlet

Duct

Clamp
(not supplied)

Stub

Asko dryers have a "T-style" 
exhaust vent that allows you to 
connect the duct on the rear, on 
the left, or on the right side

The duct must not be assembled with screws 
or other fasteners that extend into the duct 
and catch lint.

To connect the exhaust duct to the rear outlet

To connect the exhaust duct to the rear 
outlet, follow the steps below:
1.  Push the duct onto the stub pipe and 

secure it with a clamp

2.  With the duct attached, insert the stub 

pipe into the hole. It should snap into place.

3.  After you push the dryer into place, check 

for kinks in the duct.

NOTE!

•  Excessive duct length and too many bends 

can impede drying performance. We 
recommend that you cut off any excess 
exhaust duct and run the duct with as few 
bends as possible. Make any necessary bends 
as gentle as possible.

NOTE!

•  Maximum duct length of 60 feet. A 

maximum of 4 elbows may be used, but 4 
feet of duct must subtracted from the total 
vent length for every 90° elbow used.

Отзывы: