background image

© 2020 ASCO Power Technologies. All Rights Reserved

5

IO-75053

01/2020

For access to self-service tools and chat support visit se.com/us/en/work/support  or call 1-888-778-2733 for technical assistance

Model 247 (Islatrol RM Series)

Surge Protective Device (SPD)

Model

247120NF015ALCN0

247120NF020ALCN0

Operating Voltage

120 VAC

Operating Current

15 Amp

20 Amp

Operating Frequency

50/60 Hz

Peak Surge Current

20 kA/mode, 40 kA/phase

EMI/RFI Filtering

60dB Max

LED Indicators (Green)

Power On, Ground OK, Surge Circuit OK

Digital Meter

Voltage, Amps, Watts, VA, Hz, PF, Kwh, and 

Clock

Input Power

SJT 14/3C Power 

Cord (9ft) with NEMA 

5-15P Plug

SJT 12/3C Power 

Cord (9ft) with NEMA 

5-20P Plug

Output Receptacles

Front – (2) NEMA 

5-15R Back – (10) 

NEMA 5-15R

Front – (2) NEMA 

5-20R Back – (10) 

NEMA 5-20R

SPD Technology

Thermally Protected MOVs

Overcurrent Protection

Rocker Switch / Circuit Breaker

Response Time

< 5ns

Dimensions (in/mm)

1.75 x 19.0 x 3.8 in. (1U)

[44.45 x 482.6 x 96.52 mm]

Weight (lbs/kg)

3.2 lbs [1.45 kg]

Limited warranty

5 Year

Agency Approvals

UL 1449 Recognized

UL 1283 Recognized

UL 1363 Recognized

General Technical 

Specifications

Содержание 247120NF015ALCN0

Страница 1: ...Surge Protective Devices Installation Operation Manual Model 247 ...

Страница 2: ...mbol It is used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardou...

Страница 3: ...uctor to connect this equipment to the power system ground Do not exceed 15 Amps continuous current for 247120NF015ALCN0 Do not exceed 20 Amps continuous current for 247120NF020ALCN0 Failure to follow these instructions will result in death or serious injury WARNING This product can expose you to chemicals including DINP which is known to the State of California to cause cancer and DIDP which is k...

Страница 4: ...N button to start stepping up the current in 1 amp increments Once the desired amperage is reached press the SET button to save The display will then flash if the load current limit is exceeded Over Voltage will be indicated on the display by OUP and will occur when the input voltage is above 145 volts Over Current will be indicated by a blinking screen when the input current exceeds the selected ...

Страница 5: ...x LED Indicators Green Power On Ground OK Surge Circuit OK Digital Meter Voltage Amps Watts VA Hz PF Kwh and Clock Input Power SJT 14 3C Power Cord 9ft with NEMA 5 15P Plug SJT 12 3C Power Cord 9ft with NEMA 5 20P Plug Output Receptacles Front 2 NEMA 5 15R Back 10 NEMA 5 15R Front 2 NEMA 5 20R Back 10 NEMA 5 20R SPD Technology Thermally Protected MOVs Overcurrent Protection Rocker Switch Circuit B...

Страница 6: ...se com us en work support or call 1 888 778 2733 for technical assistance Model Cross Reference MODEL Former Model Name APPLICATION 247120NF015ALCN0 Islatrol RM 115 10RM 120 VAC 15 Amp 5 15P x12 5 15R 247120NF020ALCN0 Islatrol RM 120 10RM 120 VAC 20 Amp 5 20P x12 5 20R Model 247 Islatrol RM Series Surge Protective Device SPD ...

Страница 7: ...es All Rights Reserved 7 IO 75053 01 2020 For access to self service tools and chat support visit se com us en work support or call 1 888 778 2733 for technical assistance Model 247 Islatrol RM Series Surge Protective Device SPD ...

Страница 8: ... en work support 1 888 778 2733 While every precaution has been taken to ensure accuracy and completeness in this literature Schneider Electric assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions ...

Отзывы: