Installation Manual
SERIES 300 Quick Connect Power Panel
381333-476 A
3
Prior to Installation: Site Preparation
Prepare installation site according to local codes.
The ASCO SERIES 300 Quick Connect Power Panels are to be
set on an exterior pad and secured to a building or secured to
a pad using 3/8“ fasteners (See Figure 1).
The surface where the ASCO SERIES 300 Quick Connect
Power Panel is to be secured must be capable of supporting
the weight of the cabinet as well as the cable attached to it.
The following should be taken into consideration when locating
the ASCO SERIES 300 Quick Connect Power Panel:
-
The ASCO SERIES 300 Quick Connect Power Panel is
designed for exterior operation ONLY
-
Identify and meet local codes and local Authority Having
Jurisdiction (AHJ)
-
To prevent carbon monoxide poisoning from improperly
ventilated generator emissions, the Power Panel must be
mounted outdoors only. The mounting location is to be
carefully selected to allow convenient connection to a
generator and located a suitable distance away from any
building openings or HVAC inlets.
-
Proper clearance must be allowed in front of the ASCO
SERIES 300 Quick Connect Power Panel to allow for
opening of access doors and attachment of externally
connected cables. This distance should be no less than six
(6) feet from the face of the panel.
-
While lock protection is provided, access by unauthorized
personnel and vandals should be taken into consideration
when locating this device.
Shipment: Unpacking and Inspection
Be careful in the use of sharp object when cutting
packaging as damage to the outer enclosure may result.
Perform a visual inspection to ensure the door and all hasps
are in functioning condition and that the panel integrity is intact.
Secure with 3/8” fastener
s
Figure 1-Bottom View