User’s Manual
475 Mini Crate Series
W-I
e
–
N
e
-R
Plein & Baus GmbH
12/11/2017
20
optional sensors 1 to 8
sensorWarningThreshold.temp1
…temp8
integer
R/W
Warning temperature limit
sensorFailureThreshold.temp1 … temp8
integer
R/W
Failure temperature limit
sensorAlarmTh
reshold.temp1 … temp8
integer
R/W
Alarm temperature limit
fanNominalSpeed.0
integer
R/W
Set fan speed
fanSpeed.1
integer
R
Measured speed of fan
3.2
SNMP Control Examples
Following examples are given to get information for power supply output channel u0 and to read /
program temperature limits:
Read measured voltage:
C:\Users\Andreas Ruben>snmpget -v 2c -m +WIENER-CRATE-MIB -c public 192.168.0.81
outputMeasurementSenseVoltage.u0
WIENER-CRATE-MIB::outputMeasurementSenseVoltage.u0 = Opaque: Float: 5.000000 V
Read measured current:
C:\Users\Andreas Ruben>snmpget -v 2c -m +WIENER-CRATE-MIB -c public 192.168.0.81
outputMeasurementCurrent.u0
WIENER-CRATE-MIB::outputMeasurementCurrent.u0 = Opaque: Float: 3.640000 A
Read temperatures (crate is outfitted with 3 sensors at position 4,5 and 6:
C:\ >snmpwalk -v 2c -m +WIENER-CRATE-MIB -c public 192.168.0.81 sensorTemperature
WIENER-CRATE-MIB::sensorTemperature.temp1 = INTEGER: -128 deg C
WIENER-CRATE-MIB::sensorTemperature.temp2 = INTEGER: -128 deg C
WIENER-CRATE-MIB::sensorTemperature.temp3 = INTEGER: -128 deg C
WIENER-CRATE-MIB::sensorTemperature.temp4 = INTEGER: 25 deg C
WIENER-CRATE-MIB::sensorTemperature.temp5 = INTEGER: 25 deg C
WIENER-CRATE-MIB::sensorTemperature.temp6 = INTEGER: 27 deg C
WIENER-CRATE-MIB::sensorTemperature.temp7 = INTEGER: -128 deg C
WIENER-CRATE-MIB::sensorTemperature.temp8 = INTEGER: -128 deg C
Read specific temperature probe:
C:\ >snmpget -v 2c -m +WIENER-CRATE-MIB -c public 192.168.0.81 sensorTemperature.temp4
WIENER-CRATE-MIB::sensorTemperature.temp4 = INTEGER: 25 deg C
Set temperature warning level for probe 4
C:\>snmpset
-v
2c
-m
+WIENER-CRATE-MIB
-c
admin
192.168.0.81
sensorWarningThreshold.temp4 i 50
WIENER-CRATE-MIB::sensorWarningThreshold.temp4 = INTEGER: 50 deg C
Set fan speed to 3100 RPM
C:\>snmpset -v 2c -m +WIENER-CRATE-MIB -c
admin
192.168.0.81fanNominalSpeed.0 i 3100
WIENER-CRATE-MIB::fanNominalSpeed.0 = INTEGER: 3100 RPM
Change of IP address via SNMP
Содержание WIENER Mini Crate 475
Страница 2: ...WIENER Mini Crate 475 User Manual...
Страница 3: ......
Страница 37: ...User s Manual 475 Mini Crate Series W Ie Ne R Plein Baus GmbH 12 11 2017 34...