Installation manual AR-024 explosion-safe occupancy sensor
04-2022
8 / 44
E
Dimmer setting:
10
– 2,000 Lux
Preset time:
15 seconds
– 30 minutes
Supply voltage:
230 VAC ± 10%
Switch power AC1:
1,150 VA (resistive and light inductive loads)
Output:
Potential free contact
Electrical connections:
Terminals 8 x 2,5 mm²
Material:
Die cast aluminum housing (RAL 7015, slate grey),
cable glands nickel plated brass
Entries:
M20 cable glands (2x) suitable for cables from 6
– 14
mm in diameter
Sealed against moisture and dust: IP 65 according to EN 60529
Mounting bracket:
Stainless steel mounting bracket, mounting holes Ø 6,5
(4x), distance 60 x 60 mm
Ambient temperature:
-
20 ˚C to +50 ˚C
Housing dimensions (L x W x H):
120 x 120 x 195 mm (including mounting bracket,
excluding cable glands)
Sensor dimensions
65 x Ø98 mm
Weight:
1,860 g (incl. mounting bracket)
6.
Marking
The occupancy sensor complies to the European Directives for EMC and ATEX and implicit
to the Low Voltage Directive. With regard to explosion safety the occupancy sensor has been
designed and manufactured on the basis of the essential health and safety requirements of
European Directive 2014/34/EU (ATEX 114) relating to Group II Category 3GD. Harmonized
European construction standards have been applied fulfilling the essential requirements of
the directives. For more details refer to section 6 Technical data and to the Declaration of
Conformity as shown on the last page of this manual.
Example of an AR-024 occupancy sensor label
OCCUPANCY SENSOR
II 3 G Ex ec mc IIC T6 Gc
Type: AR-024
II 3 D Ex mc tc IIIC T80ºC Dc
230 VAC, IP65
Cert. Artidor 20ATEX9999X
Year: 2020
TF & Serial No.: AS123456
-20 °C < Ta < +50 °C
Artidor Explosion Safety B.V.
Emopad 38, 5663 PB Geldrop, The Netherlands, www.Artidor.com