User manual - Annex II
High Voltage Instrument Transformers | DDB/DFK/DDN/DFN
ANNEX II
SCREW
TYPE
TORQUE WRENCH SETTING (Nm)
USE
TORQUE WRENCH SETTING
M12/16/20
Fixing the insulator to the base
30 Nm
M12
Support between capacitor units
30 Nm
M12
Insulator fl ange to intermediate plate
30 Nm
M6
Connection cable between capacitor units
12 Nm
M8
Tank Lid
30 Nm
M8
Primary Terminals
20 Nm
M8
Secondary terminals (if they are of the screw type)
12 Nm
M6
Grounding (inside secondary terminal box)
12 Nm
M10
HF terminal
12 Nm
M6
Cable gland
12 Nm
M8
Terminal Block Cover
20 Nm
M6
Bottom closing lid of the terminal block
12 Nm
TIGHTENING TORQUES
NOTE: If a torque diff erent from that indicated in this table is indicated on the drawing or plates of the equipment, the torque indicated on the drawing
or plate must be applied.