background image

4

Installing Connector Blocks and Steam 

Traps on Connector blocks

Standard

The Standard connector block should be installed in piping with the flow direction stamp pointing in the correct direction as 

indicated on the connector block.

•  The trap will then be bolted to the connector block after the connector block has been installed.

•  When installing the trap to the connector block, apply 35-50 ft-lbs of torque to the bolts using a 9/16” wrench. Allow 

2.5” clearance for bolt installation and removal.

•  When starting a trap, be sure to open the valve slowly.

Note: Armstrong strongly recommends adding an upstream strainer and isolation valves upstream and downstream of the 

trap. Refer to figures 4.1 and 4.2.

IS2

The IS2 connector block should be installed in piping with the flow direction stamp pointing in the correct direction as 

indicated on the connector block.

•  The trap will then be bolted to the connector block after the connector block has been installed.

•  When installing the trap to the connector block, apply 35-50 ft-lbs of torque to the bolts using a 9/16” wrench. Allow 

2.5” clearance for bolt installation and removal.

•  When starting a trap, be sure to open the valve slowly.

Note: Armstrong strongly recommends isolation valves upstream and downstream of the trap. Refer to figures 5.1 and 5.1.

Isolation 

Valves

Strainers

Test Valve

Standard

Connector

Blowdown

Valve

Isolation 

Valves

Strainer

Standard

Connector

Test Valve

Blowdown

Valve

Figure 4.1

Figure 4.2

Содержание SH-2000

Страница 1: ...SH 2000 SH 2500 AB 3000 Bimetallic Steam Traps Installation and Operation Manual 65 SH 2500 SH 2000 AB 3000...

Страница 2: ...ld be used by qualified personnel as a guide to the installation of Armstrong SH 2000 SH 2500 And AB 3000 Bimetallic Steam Traps Selection or installation of equipment should always be accompanied by...

Страница 3: ...itical from both a performance and maintenance aspect Installation of the trap is simplified if you follow these guidelines 1 Before installing the trap ensure the line is clean Blow down any strainer...

Страница 4: ...valves upstream and downstream of the trap Refer to figures 4 1 and 4 2 IS2 The IS2 connector block should be installed in piping with the flow direction stamp pointing in the correct direction as ind...

Страница 5: ...nnector block after the connector block has been installed When installing the trap to the connector block apply 35 50 ft lbs of torque to the bolts using a 9 16 wrench Allow 2 5 clearance for bolt in...

Страница 6: ...c Pipe line or elbows plugged d Pressure reducing valve out of order e Isolation valves are off closed Caution Superheated steam is invisible Do not place objects directly in the path of trap discharg...

Страница 7: ...l need to be installed AB 3000 Remove the steam trap from the connector block by taking the two bolts out Unscrew and lift the cap Unscrew and replace the bimetallic element The distance between the f...

Страница 8: ...he products supplied by Armstrong however caused and whether such claim is based upon warranty contract negligence strict liability or any other basis or theory is limited to Armstrong s repair or rep...

Отзывы: