The plate pack is re-tightened by tightening the 

clamping bolts. Care should be taken to ensure 

that these clamps are tightened as uniformly as 

possible, i.e. the frame plates will be parallel as 

possible when tightening. Avoid end plate 

skewing greater than 10mm. These clamps 

should be tightened until the correct ‘A’ 

dimension is achieved. (See Fig. 1 for details) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘A’ for 032 plates = total number of plates x 2.9mm 

‘A’ for 150 plates = total number of plates x 2.5mm 

 

The following information is required when ordering 

spare plates and gaskets. 

 

1. 

The equipment serial number and model type. 

 

2. 

The quantity and type of plates (number of port 

holes and position). 

 

3. 

The quantity and type of gaskets (A, B or D 

gaskets). 

 

 

 

Electrical 

 

The Response

?

 control system is designed to operate 

for long periods with only the following checks. 

 

At 6 monthly intervals check:- 

 

1. 

The pump/s are running smoothly and are  not 

noisy or vibrating. 

 

2. 

The pump seals are not leaking. 

 

3. 

The electrical installation thoroughly for defects. 

Ensure that the earth connections are making 

good contact and all terminal screws are tight. 

 

4. 

The valve actuator is running smoothly and not 

noisy. 

 

 

Spares & Service 

 

    Only replace parts with original Armstrong            

    Holden Brooke Pullen spares. 

 
 

 

 