Rada Intelligent Care  

MX1 Wall Mounted Tap 

Installation Operation & 

Maintenance Manual 

494-EN V1.6

Please read and save these instructions

Содержание RADA MX1

Страница 1: ...Rada Intelligent Care MX1 Wall Mounted Tap Installation Operation Maintenance Manual 494 EN V1 6 Please read and save these instructions ...

Страница 2: ...ional com 2 Table of Contents General 3 Important Safety Information 3 Specification 4 Factory Default Settings 5 Pack Contents 8 Dimensions 9 Installation Requirements 10 Installation 11 Commissioning 18 Operation 19 Fault Diagnosis 20 Maintenance 26 Spare Parts 30 Limited Warranty and Remedy 34 ...

Страница 3: ...es Approved Codes of Practice The use of the word failsafe to describe the function of any thermostatic mixing valve is both incorrect and misleading In keeping with every other mechanism it cannot be considered as being functionally infallible Malfunction of thermostatic mixing valves can be detected by the use of proper temperature checking and maintenance routines Certain types of system can re...

Страница 4: ...V Pollution Degree 2 2 Rated Impulse Voltage 2 5 kV 18 V Performance Factory pre set temperature 102 2 F 39 C Factory pre set temperature range 98 6 F 105 8 F 37 C 41 C Programmable temperature range 91 4 F 113 F 33 C 45 C Full cold can be selected during programming Water Supply Minimum dynamic pressure 14 5 Psig 100 kPa 1 0 bar Maximum dynamic pressure 72 5 Psig 500 kPa 5 0 bar Maximum static pr...

Страница 5: ...tory Programmed Typical Range 180 220 13 Pin 0001 9999 Permisable Re entry of 5945 Not Permitted 14 Tap Interface Info Field 15 Operational State Enable Enable Enable Disable 16 Tasks Apply Changes to Valve Undo Changes 1 Valve Setup 5 Outlet Setup 1 Type Info Field 2 Sub Type On Off On Off On Off Timed Blocking N A 3 Outlet Selection Info Field 4 Full Cold Mode Disabled Disabled Start Cold Enable...

Страница 6: ...Cold Flush 0 0 0 10 Seconds min 11 Tasks Apply Changes to Valve Undo Changes 1 Valve Setup 7 Cold Flush Setup 1 Activation Manual Manual Manual Automatic 2 Type Disabled Disabled Disabled Standard 3 Activation Time 04 00 Hrs 04 00 Hrs Time 24 Hr Clock 4 Duration 2 Mins 2 Mins 5 S 10 Mins Seconds Min 5 Frequency 1 Per 3 Days 1 Per 3 Days 1 Hr 1 Week Hrs Day 1 Week 6 Schedule Auto Populated Fiel d 7...

Страница 7: ...onds Min 10 Flow Test Start Stop 11 Flow Rate 100 100 10 100 12 Taks Apply Changes to Valve Undo Changes 1 Valve Set Up 8 Thermal Disinfection Setup 1 Activation Manual Manual 2 Type Disabled Disabled Disabled Standard Exponential Standard Cold Exponential Cold 3 Duration 20 20 1 30 Mins 4 Minimum Temperature 140 F 60 C 140 F 60 C 140 F 60 C Upper deg F C 5 Upper Temperature 140 F 60 C 140 F 60 C ...

Страница 8: ...East Africa China Pacific Rim armstronginternational com 8 1 Tap q 1 Backplate q 1 Rada Disable Key q 2 Connectors q 2 Nuts q 2 Screws q 1 Template q 4 Fixing Screws q 4 Wall Plugs q 1 Power Supply q 2 Flow Regulator Filter Assemblies q Pack Contents ...

Страница 9: ...m 7 78 200 mm 41 85 7 mm 7 83 199 mm 10 31 262 mm 3 15 80 mm 1 57 40 mm 1 02 26 mm 6 69 170 mm 30º 1 14 29 mm 3 07 78 mm PSU Mains Cable 6 6 2 m PSU TAP PSU 12V Cable Extension Cable Total Cable Run 3 87 1 18 m Total Cable Run with Extension Cable 12 07 3 68 m Product Tail 3 3 1 0 m 8 2 2 5 m 0 59 0 18 m Connection to Power Supply Unit ...

Страница 10: ...ue The Rada MX1 60 wall mounted tap is designed for panel mounting scrub trough Specifically where rear access is available NOT suitable for solid wall installation The filter flow regulator unit must be fitted Hot Red Dot Cold Blue Dot The arrow indicates flow direction The unit must be accessible for service Installation Requirements ...

Страница 11: ...ternational com 11 0 59 Ø15 mm 0 98 Ø25 mm 0 078 Ø2 mm Installation of the Tap on the Stud wall and IPS panel Use the installation template provided level and mark the positions of the holes For Correct Height Refer to HBN00 10 Part C Drill the holes to the dimensions shown Installation 1 2 ...

Страница 12: ...ernational com 12 3 4 Secure the backplate using the supplied fixing screws DO NOT overtighten Fit the inlet connectors with isolation hex facing downwards aligning with the holes in the backplate Attach the backnuts supplied leaving approx 10 15 mm float allowing access to the spanner flats ...

Страница 13: ...dle East Africa China Pacific Rim armstronginternational com 13 Make the plumbing connections DO NOT use jointing paste when making plumbing connections Make the plumbing connections DO NOT use jointing paste when making plumbing connections 5 6 ...

Страница 14: ... Middle East Africa China Pacific Rim armstronginternational com 14 7 8 1 min Flush the pipework Install the filter flow regulator unit DO NOT use jointing paste when making joints Red Dot Hot Blue Dot Cold The arrow indicates flow direction ...

Страница 15: ...North America Latin America India Europe Middle East Africa China Pacific Rim armstronginternational com 15 9 Connect flexible tails to filter flow regulator units ...

Страница 16: ...North America Latin America India Europe Middle East Africa China Pacific Rim armstronginternational com 16 Open supply isolators Flush pipework 1 min 2 5 mm 18 mm H2O H2O 10 11 ...

Страница 17: ...in America India Europe Middle East Africa China Pacific Rim armstronginternational com 17 12 Secure the tap using the supplied screws DO NOT overtighten Open the isolator on the check valve filter housing ON ON a 13 b ...

Страница 18: ...al com 18 Pull off the cover from tap The Rada MX1 wall mounted tap will operate to factory settings when first installed Download the RADA AP1 from the Apple App Store and follow the on screen instructions Note Run the tap for 30 seconds in order for self calibration to take place 14 Commissioning ...

Страница 19: ...iddle East Africa China Pacific Rim armstronginternational com 19 The Rada MX1 wall mounted tap will operate to factory settings when first installed Download the RADA AP1 from the Apple App Store and follow the on screen instructions Operation ...

Страница 20: ...valves blocked Check and remedy Inlet check valves flow regulators installed the wrong way around Check and remedy Outlet spout hose or handset blocked Check and remedy Reversed inlet supplies Check and remedy Inlet water pressure too low Check specification Blocking time set Commission Blocking time using the communication app Digital Mixing Valve air locking Check for correct installation practi...

Страница 21: ...peat commissioning procedure and rearrange pipework to avoid airlock forming Digital Mixing Valve failure Contact Rada Keeps cutting out Product has entered an error mode indicated by a flashing spanner symbol Refer to Error Log Inlet water supply isolators not fully turned on Check and remedy Inlet filters or check valves blocked Check and remedy Outlet spout hose or handset blocked Check and rem...

Страница 22: ...pecifications Outlet pipe run is too long Ensureoutletpipeworkisthermallylagged Digital Mixing Valve failure Contact Rada Outlet temperature is too hot or fluctuates Temperature adjustment set too high Decrease temperature control Some models only Blend temperature set too high Re commission blend temperature using RADA AP1 Hot inlet water supply temperature is too hot Reduce hot inlet water tempe...

Страница 23: ...ring Protective film not removed from product Remove protective film Dirty sensor window Clean sensor window Reflective surfaces Infra Red sensors activated by reflective surfaces such as polished basins Hi Vis jackets and mirrors Ambient light conditions Direct sunlight or constant shadowing of the sensors to be reduced Digital Mixing Valve failure Contact Rada Water leaking from product Damaged ...

Страница 24: ...Non Product fault Thermistor has seen an unsafe blend temperature and has gone in to a thermal shutdown to protect the user Valve will self clear fault Inlet filters or check valves blocked Check and remedy Obstruction in inlet water supplies e g kinked inlet hose Check and remedy Hot inlet water supply temperature is too hot Reduce hot inlet water temperature to between 131 F and 149 F 55 C and 6...

Страница 25: ...turning electrical supply off for 30 seconds then re apply power Loose internal wiring connections Thermistor Ensure all wiring connections are securely made Thermistor failure Contact Rada Unconfigured A to D Read Error RAM error EE Error External EE error RTC Fault Flash Error Scheduler Error IR not calibrated Software failure Re set the product by turning electrical supply off for 30 seconds th...

Страница 26: ...steel enamel plated or plastic fittings These finishes should be cleaned using a mild washing up detergent or soap solution rinsed and then wiped dry with a soft clean cloth Note Run the tap for 30 seconds in order for self calibration to take place Enter cleaning mode Scan the Rada key over the spout to enter exit cleaning mode Remove the flow insert using 5 16 8mm hexagonal wrench Change the flo...

Страница 27: ...China Pacific Rim armstronginternational com 27 Isolate water supplies Disconnect tails Remove filter Separate the filter unit lower portion can remain attached to supply elbow 1 2 3 4 Clean the filter 5 Clean replace filter Refit the components in reverse order ...

Страница 28: ...North America Latin America India Europe Middle East Africa China Pacific Rim armstronginternational com 28 1 2 3 ...

Страница 29: ...North America Latin America India Europe Middle East Africa China Pacific Rim armstronginternational com 29 This Page is Intentionally Left Blank ...

Страница 30: ...Europe Middle East Africa China Pacific Rim armstronginternational com 30 D128117 A D128106 D129225 D128120 A A A A A D128110 D128122 D128115 D128111 A A D128118 x 1 D128119 x 10 D128108 A A A A A D128109 1 97 50mm A D128127 Spare Parts ...

Страница 31: ... MX1 60 D128108 Mount Printed Circuit Board MX1 60 D128109 Inlet 1 each MX1 60 D128110 Back Plate MX1 60 D128111 Cap 1 pair MX1 60 D128115 Thermistor MX1 60 D128117 Interface Cover Temperature MX1 60 D128118 Flow Insert 1 pack MX1 60 D128119 Flow Insert 10 packs MX1 60 D128120 Power Supply Cable MX1 60 D128122 Back Nut 1 pair MX1 60 D128127 Screw Pack Noted as A below MX1 60 D129225 Valve Assembly...

Страница 32: ...ca India Europe Middle East Africa China Pacific Rim armstronginternational com 32 Spare Parts continued D128114 D35448 x3 D129223 8 2 2 5m D128128 x2 D128129 x20 D128132 x2 2L and 6L Min D129224 D128130 2 L min D128131 6 L min ...

Страница 33: ...pply Unit MX1 60 D128128 Filter Insert pack of 2 MX1 60 D128129 Flow Insert pack of 20 MX1 60 D128130 Filter Flow Regulator Assembly Hot 1 each MX1 60 D128131 Filter Flow Regulator Assembly Cold 1 each MX1 60 D128132 Flow Regulator Pack One 2L One 6L MX1 60 D129223 Cable Extension Assembly MX1 60 D35448 Disable Key Pack x3 3 each MX1 60 Spare Parts continued ...

Страница 34: ...s repair or replacement of the part or product excluding any labor or any other cost to remove or install said part or product or at Armstrong s option to repayment of the purchase price As a condition of enforcing any rights or remedies relating to Armstrong products notice of any warranty or other claim relating to the products must be given in writing to Armstrong i within 30 days of last day o...

Страница 35: ...North America Latin America India Europe Middle East Africa China Pacific Rim armstronginternational com 35 Notes ...

Страница 36: ...a Pacific Rim armstronginternational com 494 EN V1 6 Armstrong International Inc Rada Installation Operation Maintenance Manual Designs materials weights and performance ratings are approximate and subject to change without notice Visit armstronginternational com for up to date information ...