4.2.1 alarms
Alarm
Description
Possible causes
Emergency alarm
Indicates operator activated field emergency
switch/button through hardwire or
bas
.
• Field emergency
• Critical conditions
Pump n alarm
Indicates pump n is in alarm.
Any pump alarm will trigger this alarm.
Pump n run feedback
alarm
Indicates
plc
didn’t detect the pump run feed-
back from pump n after commanding it to start.
• vfd
not configured for serial communication
• Loose or broken wire from
vfd
• Incorrect
vfd
type selected on
ips
• Impeller is stuck
Drive n communication
alarm
Indicates
vfd
of pump n failed to communicate
with
plc
.
• vfd
not configured properly
• Communication card not installed properly
• Incorrect or faulty wiring
Pump n drive fault alarm
Indicates
vfd
of pump n is reporting a fault.
vfd
over current or other problem. Check
vfd
local display.
Flow transmitter fail
alarm
Indicates flow transmitter is out of range.
• Connection to transmitter is short or open circuited
• Damaged
plc
analog input
• Loose or broken wire from transmitter
• Damaged transmitter
Zone n transmitter
alarm
Indicates transmitter of zone n is out of range.
• Connection to transmitter is short or open circuited
• Damaged
plc
analog input
• Loose or broken wire from transmitter
• Damaged transmitter
All zones transmitter
alarm
Indicates all zones transmitters are out of range. All zone sensors are in alarm.
Temperature sensor fail
alarm
Indicates temperature sensor for Temp Control
Valve is out of range.
• Connection to sensor is short or open circuited
• Damaged
plc
analog input
• Loose or broken wire from sensor
• Damaged sensor
Chiller/boiler flow below
minimum alarm
Indicates system flow is less than chiller/boiler
total minimum set value.
• Incorrect calibration of flow meter
• Bypass valve not open
• Flow obstruction in the pipe
Chiller/boiler flow above
maximum alarm
Indicates system flow is greater than chiller/
boiler total maximum set value.
• Incorrect calibration of flow meter
• Bypass valve not close
• Incorrect design sensorless data