26
HC-4100 / HC-4145 / HC-4300
(See page 28 for HC-4500)
HC-4100/4145/4300
Component
Voltage
Resistance
Fill Valve
24 vac
18
Ω
Drain Valve
24 vac
10
Ω
Contactor
24 vac
7-9
Ω
Thermocouple in Heating
Element
—
0.51
Ω
208 & 380 vac 15/30 kW
220 vac
9.2 - 10.7
Ω
240 vac 15/30 kW
240 vac
10.9 - 12.6
Ω
480 vac 15/30 kW
277 vac
14.5 - 16.8
Ω
600 vac 15/30 kW
346 vac
22.7 - 26.3
Ω
208 & 380 vac 9/18 kW
220 vac
15.3 - 17.7
Ω
240 vac 9/18 kW
240 vac
18.2 - 21.1
Ω
480 vac 9/18 kW
277 vac
24.3 - 28.2
Ω
600 vac 9/18 kW
346 vac
37.9 - 43.9
Ω
120 vac
13.6
Ω
across H1 - H2
15.1
Ω
across H3 - H4
208 vac
22
Ω
across H1 - H2
240 vac
29
Ω
across H1 - H2
380 vac
77
Ω
across H1 - H2
480 vac
125
Ω
across H1 - H2
600 vac
194
Ω
across H1 - H2
Power Tansformer
(secondary)
All
Voltages
0.6
Ω
across X1 - X3
0.4
Ω
across X1 - X2
Power Tansformer
Note: All measurements should be made with the main
power off and the wires to the component being tested
Resistance Values of Components
Heating Elements
Item
No.
Steam Generator
Part No.
34
Tank
D2041
35
Access Cover Hold Down Knobs (Qty 2)
A19697
36
Tank Access Cover
D4244
37
Tank Access Cover Gasket
A21909
38
Ionic Beds (5 required)
B5213
Item
No.
Miscellaneous
Part No.
41
Lock and (2) Keys for Cabinet
A10789
43
2-3/8" ID x 12" EPDM Hose Cuff (not shown)
B2851A
43
2" ID x 12" EPDM Hose Cuff (not shown)
B2851
44
1-1/2" ID x 9-5/8" EPDM Hose Cuff (not shown)
B2250
45
1" ID x 18" Tygon Drain Tube (not shown)
A9620-1
46
Hardware Kit
B5287
—
Annealed Tank
D2171
Содержание HumidiClean HC-4100 Series
Страница 23: ...23 HC 4100 4145 4300 Series HumidiClean Typical Wiring Schematic...
Страница 24: ...24 HC 4500 Wiring Schematic...