installation &   

oper ating instructions

E.2 Series high efficiency    

 

circulator

6

5.0  pump replacement in an existing  

 

installation

5.1  complete pump

1

   Ensure that electric power is disconnected and locked out. 

Loosen the screw from the terminal box cover and remove 
the cover. Disconnect the supply wires from the circulator 
only, leaving the capacitor wires connected.

All servicing personnel should be equipped with 
proper personal protective equipment.

2

  If valves have been installed, on the suction and discharge  

sides of the pump, close them before attempting to remove 
the circulator from the volute. If no valves have been installed 
it may be necessary to drain the system.

Allow water to cool to 

100°f (40°c)

 before draining 

the system. It is best to leave the drain valve open 
while working on the system.

3

  To relieve any residual pressure which may be present in  

the pump body, loosen the flange bolts and gently move  
the pump body back and forth to allow the pressurized  
water to escape.

note: 

Place a pan under the pump to collect the drain water.

4

  If the entire volute is needed to be removed, then remove 

the flange bolts and nuts. The entire circulator can then be 
removed from the piping system.

5

  Install the 

e.2

 series circulator where there will be sufficient   

  room for inspection and service. It is recommended that  

 

  isolation valves be installed on both the suction and  

 

  discharge sides of the circulator for future servicing. This    
  eliminates the need for draining the system when working    
  on the circulator (for example, when replacing the    

 

  mechanical seal).

6

  Install suction and discharge flanges on the pipe ends. The    

  use of Teflon tape sealer or a high quality thread sealant is    
 recommended.

7

  Pipe strain can be minimized by the use of pipe hangers  

  near the pump, positioned to support the suction and  

 

  discharge piping.
To wire the 

e.2

 series circulator, follow steps C through G in the 

Electrical Wiring section above, noting that electrical supply 
and grounding wires must be rated for at least 

194°f (90°c)

.

5.2  motor end only

1

  Turn off the pump leaving it installed in the line .

Ensure electrical power is disconnected and locked out .

3

  Close the water supply at the points closest to the pump's    

 inlet and outlet .

4

  For safety, allow water to cool to 

100°f (40°c)

 before  

 

 draining the system. It is best to leave the drain valve open    
 while  working on the system.

5

  Bleed the water pressure from the pump.

6

  Place a pan under the pump to collect the drain water.

7

   While holding the motor body, loosen the four bolts that  

 

 attach the motor to the pump casing (volute). Start with the   
 two bottom bolts first and remove them, then slowly loosen   
 the top two bolts. Allow the water to drain from the bottom   
 of the pump. When the water has finished draining, remove   
 the two top bolts. Remove the motor straight out from the    
 volute being careful of its attached impeller. The motor is    
 heavy, do not drop it.

8

  Install new casing gasket .

9

  Install new motor end (with impeller and seal kit).

10 

Tighten four motor end bolts in a crisscross pattern and  

 

 tighten evenly to 

60

 in/lbs.

11

  Open isolation flanges or fill the system with water before    

 starting circulator.

12

 To wire the 

e.2

 series circulator, follow steps C through G in   

 the Electrical Wiring section above, noting that electrical    
 supply and grounding wires must be rated for at least  

 

 

194°f (90°c).

6.0 mechanical seal replacement

1

   Follow steps 

1

 through 

4

 in section 

Existing pump removal  

from system piping.

2

  While holding the motor body, remove the bottom two  

bolts that attach the motor to the pump casing (volute),  
then slowly loosen the top two bolts. Allow the water to 
drain from the bottom of the pump. When the water has 
finished draining, remove the two top bolts. Remove the  
motor  straight out from the volute being careful of the  
attached impeller. 

Handle with care  

The motor is heavy, and possibly hot,  

do not

 drop it!

3

  While holding the rotor very tightly by hand or a gloved hand 

only, unscrew the impeller nut off the motor shaft by turning 
it clockwise (i.e. opposite to most bolts and nuts). Place the 
motor on its back, with the shaft up.

 Remove the rotary part of the mechanical seal by gently  

pulling it off the shaft. If it is too tight use two small flat 
bladed screwdrivers to gently pry it off the shaft by placing 
the flat side of the blades onto opposite sides of the  
mechanical seal.

Содержание E.2 Series

Страница 1: ...E 2 Series High efficiency circulator Installation and operating instructions File No 10 84 Date july 04 2018 Supersedes 10 84 Date january 25 2018...

Страница 2: ......

Страница 3: ...ectrical wiring 4 3 0 Start up 5 4 0 Preventive maintenance inspection 5 5 0 Pump replacement in an existing installation 6 5 1 Complete pump 6 5 2 Motor end only 6 6 0 Mechanical seal replacement 6 7...

Страница 4: ...ecommends a thorough flush of the hydronic system ensuring removal of all foreign materials This pump should be installed in a well lit location with good access Installation personnel must be qualifi...

Страница 5: ...4 230 v installations pump motor Pump motor thermally protected To auxilliary control if required Fusible disconnect or circuit breaker by others l1 l2 Typical wiring diagram for single phase 230 v 5...

Страница 6: ...ed in the line 2 Ensure electrical power is disconnected and locked out 3 Close the water supply at the points closest to the pump s inlet and outlet 4 For safety allow water to cool to 100 f 40 c bef...

Страница 7: ...loth and alcohol to ensure the surface is clean 14 Install the new rotating seal element and spring assembly by gently pushing it graphite ring first over the installation tool and onto the shaft unti...

Страница 8: ...ressure 1034 kPa All models Electrical motor data model e7 2 e7 2b e9 2 e9 2b e12 2 e12 2b e14 2 e14 2b e22 2 e22 2b e33 2 e33 2b Nominal input voltage range 50 hz 220 240vac 220 240vac 220 240vac 220...

Отзывы: