6
Designs, materials, weights and performance ratings
are approximate and subject to change without notice.
Visit
armstrong
international.com for up-to-date information.
Specifications
Operating Specifications
Steam Supply Pressure
2-15 PSIG (0.14-1 barg)
Water Supply Pressure
20-150 PSIG (1.4-10 barg)
Minimum Inlet Supply Water Temperature
34°F (1°C)
Set Point Range (DRV)
81-158°F (27-70°C)
Minimum System Recirculation Flow
10 GPM (38 LPM) for DRV80 or 50 / 5 GPM (19 LPM) for DRV40
Minimum System Draw Off
0 GPM / LPM
Minimum Distance to First Outlet
25 ft (7.62 m)
Minimum Recirculation Loop Temperature Loss
2°F (1°C)
General Specifications
Control Circuit Fuse
3 A (5A w/ SAGE®)
Enclosure Protection Rating
Electrical Enclosure – Nema 12
DRV – Nema 3S
Signal Cable Fittings (DRV)
3/8” liquid-tight, conduit fitting
Battery (DRV)
Qty. 2, type CR-P2, 6V rating
Power Supply Requirements
120/240 VAC / 50-60 Hz / 1 Ph.
Insulation Jacket
Aspen Aerogel Pyrogel (R-Value = 12.5)
Component
Material
Heat Exchanger Shell
316 Stainless Steel, ASME “U” Stamped
Heat Exchanger Tube Bundle
3/4” x 20 BWG Copper
Heat Exchanger Tube Sheets
304 Stainless Steel
Integral Supply Pipe Work
“Lead-free” brass/Type L copper
Integral Valves and Fittings
“Lead-free” brass or bronze
Condensate Piping
Cast iron & carbon steel
DRV Body
AISI 316L Stainless Steel
Technical Specifications
Single-Wall, Heat Exchanger