Armstrong AM-91A Скачать руководство пользователя страница 3

3

Step 4.  Install the Armstrong Steam Trap

 and connect 

the trap to the return header.  It is important:

A.  To provide a dirt pocket ahead of the trap as 

shown in the drawings.

B.  To make sure the return header pressure is well 

below the steam supply pressure.  

Never connect 

a humidifi er trap to a line carrying returns from 
high pressure traps.

Step 5.  Install Fan and Motor

 of AMAF, AMEF, and FSA 

units.  The bracket is located on the side opposite the 
steam discharge outlet in the humidi

fi

 er cap.  Cap screws 

are provided.

Step 6.  Make Electric Connections for AMEF model fan 
motors.

  Electrical connections are shown in double dash 

lines in Fig. 3-2.

A.  If automatic control of the fan motor is desired, in-

stall a pneumatic-electric relay.  The relay should 
be set to start fan with a 2 psi air signal.  
See Fig. 3-2.

P.R.V. Installation. Reducing Valves. 

Where the steam 

pressure available for humidi

fi

 ers is too high, a reducing 

valve of the single-seated or dead-end type should be 
used. The reducing valve should be at least 10 ft. from the 
humidi

fi

 er.  If the supply line is more than 20 ft. long, pro-

vide a drip pocket and extra trap just ahead of the pressure 
reducing valve.

Relief Valve. 

A pressure relief valve between the humidi

fi

 er 

and pressure reducing valve is a good insurance.  Humidi-

fi

 er bodies are only rated for 60 psig steam service.

Pressure Gage. 

A pressure gage or connection for install-

ing a gage between reducing valve and the humidi

fi

 er may 

save its cost many times over.

Air and Electrical Connections

10' Min.

Strainer

Steam

Trap

Steam

Trap

Steam 

Supply

Dirt

Pocket

PRV

Relief

Valve

Pressure Gage

To Low
Pressure
Return

Check

Valve

Figure 3-1.

Motor

Compressed air hookup. Electrical connections for AMEF units are shown.  For AMAF model omit electric.

Compressed air hookup showing air powered fan and air line accessories for AMAF units.

Wiring diagram for standard 120V or 
240V FSA or VSA Humidifiers.

Wiring diagram for 120V or 240V VSA 
Humidifier with 24V line to humidistat.

Steam In

Steam Trap

Steam

Trap

Pneumatic
Temperature
Switch

Pneumatic 
Temperature Switch

Air Supply

Oiler

Air Fan Assembly

Steam In

Humidity

Controller

Filter

Steam
Out

120 V 240 V Line In

P.E. Switch

Humidity

Controller

Hand
Switch

Armstrong A-8581-A 
(HC-101) Humidity 
      Controller

Armstrong A-8581-A 
(HC-101) Humidity 
     Controller 24 V

Power Source

Power Source

Solenoid Coil

Solenoid Coil

Temp. Switch

Temp. Switch

Switch

Fan 

(when used)

Junction

Box

Junction

Box

Relay

Air
In

Switch

Fan 

(when used)

Figure 3-4.

Figure 3-3.

Figure 3-5.

Figure 3-2.

Содержание AM-91A

Страница 1: ...spring range is specified AM VSA Models AMEF AMAF FSA Models Figure 1 1 Figure 1 2 Dimensions Armstrong Area Humidifiers Fig 1 1 VSA AM models do not have fans Fig 1 2 FSA AMEF models have electrically operated fans AMAF models utilize air powered fans Installation Procedure B C D F J E H G C D F B J E Table 1 1 Model No B C D E F G H J AM 91A 15 15 16 3 3 8 3 13 16 6 1 16 3 1 16 13 1 4 AMAF 91A 1...

Страница 2: ...1 1 4 1 1 4 1 1 4 3 4 Steam Pipe Capacities For computing ability of piping to deliver an adequate supply of steam to humidifier Capacities shown are in pounds per hour Table 2 2 Steam Pipe Capacity at 5 psi Pipe Size in Pressure drop psi per 100 ft of pipe length 1 8 1 4 1 2 3 4 1 1 24 31 44 54 62 1 1 4 52 68 97 120 140 1 1 2 81 100 150 180 210 2 160 210 300 370 430 2 1 2 270 350 500 610 710 Tabl...

Страница 3: ...ve Relief Valve A pressure relief valve between the humidifier and pressure reducing valve is a good insurance Humidi fier bodies are only rated for 60 psig steam service Pressure Gage A pressure gage or connection for install ing a gage between reducing valve and the humidifier may save its cost many times over Air and Electrical Connections 10 Min Strainer Steam Trap Steam Trap Steam Supply Dirt...

Страница 4: ...r size and type of units required and the location of both humidifier and humidity controllers Sizing and location with natural ventilation These are the average industrial humidification applications with Room temperatures 65 to 80 Relative humidities 35 to 80 Natural ventilation i e infiltration around windows and doors Selection Data Required Minimum Outdoor Temperature for most jobs figure 10 ...

Страница 5: ...ges These can be determined from exhaust fan capacity where known The cu ft per hour capacity of the fans divided by the cubic feet of space to be humidified will give the number of air changes Where the capacity of fan or fans is not known air changes can be measured with velometer readings at all open doors elevator shafts etc leading to the room and with fans operating at full capacity Your Arm...

Страница 6: ...on is through a jet nozzle or by a fan How air operated units work Air operated units operate in the same manner as electric units except that they Operation Figure 6 1 utilize a pneumatic humidistat as humidity controller in the space and an air operator to open and close the steam valve Explosion hazard humidification Sizing air operated humidifiers for areas where an explosion hazard ex ists is...

Страница 7: ...with dirt 2 Return line pressure above humidifier pressure 3 Too much vertical lift 4 Wrong type of trap used 5 Second trap short circuiting the humidifier trap Operation and Servicing Humidifier Discharges Continuously Even though Humidity Has Reached Desired Level A Mechanical Trouble 1 Humidistat fails to open points frozen 2 Dirt holds solenoid plunger in open position 3 Bent solenoid tube hol...

Страница 8: ...efects or any condition or use of the products supplied by Armstrong however caused and whether such claim is based upon warranty contract negligence strict liability or any other basis or theory is limited to Armstrong s repair or replacement of the part or product excluding any labor or any other cost to remove or install said part or product or at Armstrong s option to repayment of the purchase...

Отзывы: