background image

Page 10  of  22

507635-05

Issue 2245

Compressor

Units are shipped with compressor mountings factory 

adjusted and ready for operation. Do not loosen compressor 

mounting bolts.

Roof Curb Installation

If a roof curb is used, follow the manufacturer’s installation 

instructions and be sure that all required clearances are 

observed (see Clearances section).

Prior to setting the unit on the roof curb, the shipping 

bracket located underneath the unit must be removed. 

Remove the two screws in the base rail (located on the 

front and rear sides of the unit). The four screws and the 

bracket can be discarded. See Figure 1. 

Rigging Unit

Exercise care when moving the unit. Do not remove any 

packaging until the unit is near the place of installation.

1.  Connect rigging to the unit base rails using both holes 

in each corner.

2.  All panels must be in place for rigging.
3. 

Place  field-provided  spreaders  in  place.  Spreaders 

must be of adequate strength and length (must exceed 

unit dimension by 6 inches).

Units may also be moved or lifted with a forklift. 

The 

lengths of the forks of the forklift must be a minimum 

of 42 inches.

• 

The  unit  operating  conditions  (including  airflow, 

cooling operation, ignition, input rate, temperature 

rise and venting) must be verified according to these 

installation instructions.

Clearances

All units require certain clearances for proper operation 

and service. Refer to Table 1 for the minimum clearances 

to combustibles required for construction, servicing, and 

proper unit operation.

In the U.S., units may be installed on combustible floors 

made from wood or class A, B, or C roof covering material.

In Canada, units may be installed on combustible floors. 

Units must be installed outdoors.

Do not permit overhanging structures or shrubs to 

obstruct condenser air discharge outlet.

Clearance to 

Combustibles

Clearance for 

Service Access

Front of unit

0 in.

24 in.

Back of unit

0 in.

0 in.

Left side

0 in.

24 in.

Right side 

0 in.

24 in.

Base of unit

0 in.

0 in.

Top of unit

0 in.

48 in.

For any future service, installer must provide access to 

screws of top and rear panels.

Table 1. Minimum Clearances

Shipping Bracket and Mounting Screws Must be 

Removed for Rooftop or Downflow Application

Field-Provided Lifting

Spreaders Recommended

Figure 1. 

Содержание RP16AC Series

Страница 1: ...tates the Canadian Electrical Code Part 1 CSA 22 1 latest edition in Canada and any state or provincial laws or local ordinances Local authorities having jurisdiction should be consulted before instal...

Страница 2: ...T POWER ENTRY 5 86 3 07 6 20 17 07 13 44 13 44 14 32 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENTRY POWER EN...

Страница 3: ...POWER ENTRY 14 32 4 20 3 76 6 20 17 07 18 19 18 19 6 20 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT SIDE VIEWS TOP VIEW POWER ENTRY POWER ENTRY RETURN AIR 2 11 19 49 2 39 2 33 1...

Страница 4: ...x 5 5 8 in 140 x 31 mm Opening for Power Entry Through Unit Base 3 x 13 in 76 x 330 mm 44 3 8 1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 4...

Страница 5: ...Unit Base 5 1 2 x 5 5 8 in 140 x 31 mm Opening for Power Entry Through Unit Base 3 x 13 in 76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETU...

Страница 6: ...ements NOTE CLIPLOCK CORNER DETAIL CURB PROFILE 1 1 2 1 3 4 1 11 5 8 2 1 8 14 1 3 1 2 13 1 2 44 3 8 Bottom Curb Assembly Opening for Power Entry thru base 11 5 8 5 1 2 5 3 4 3 5 8 1 3 8 17 1 4 13 7 8...

Страница 7: ...ements NOTE CLIPLOCK CORNER DETAIL CURB PROFILE 1 1 2 1 3 4 1 19 5 8 11 5 8 2 1 8 19 3 8 11 5 8 14 23 1 8 1 5 1 2 5 3 4 3 1 2 3 1 2 13 1 2 6 7 8 52 7 8 44 3 8 Insulated Panels Opening for Power Line E...

Страница 8: ...89 2 1 8 54 Built In Rain Diverter Not Shown Front Flange 8 203 NOTE Minimum Height 4 102 Built In Drip Edge Unit Base Rail Unit Base Rail Clips 4 Sides and Back Flange 6 152 Unit Base Rail Clips 4 Su...

Страница 9: ...designed to be located outdoors with sufficient clearance for free entrance to the air inlet and discharge air openings The location must also allow for adequate service access The unit must be insta...

Страница 10: ...with a forklift The lengths of the forks of the forklift must be a minimum of 42 inches The unit operating conditions including airflow cooling operation ignition input rate temperature rise and vent...

Страница 11: ...by the installer Refer to the unit rating plate for maximum over current protection and minimum circuit ampacity as well as operating voltage The power supply must be sized and protected according to...

Страница 12: ...be discarded 2 Install the duct system to the unit For downflow duct systems 1 Remove the duct covers on side of the unit Keep the screws and the covers as they will be re installed later 2 Remove th...

Страница 13: ...te drain line must be properly trapped routed to a suitable drain and primed prior to unit commissioning NOTE Install drain lines and trap so they do not block service access to the unit See Figure 4...

Страница 14: ...11 full times plus one fast or half flash At times the light may appear to flicker or glow This takes place when the control is communicating with the motor between cycles This is normal operation Rea...

Страница 15: ...ssor and outdoor fan Second stage heating is initiated when the thermostat energizes Y2 or when the outdoor ambient temperature is below the lock in temperature see Second Stage Lock In section The re...

Страница 16: ...dition NOTE Within a single room thermostat demand if 5 strikes occur the board will lockout the unit Control board 24 volt power R must be cycled OFF or the TEST pins on board must be shorted between...

Страница 17: ...brate another defrost cycle will be initiated after 45 minutes of heating mode compressor run time Once the control board is calibrated it initiates a demand defrost cycle when the difference between...

Страница 18: ...rcuits malfunctioning metering device or other system components Maintenance Before performing maintenance operations on the system shut off all electrical power to the unit Turn off accessory heater...

Страница 19: ...18 342 366 392 419 446 475 504 60 258 277 298 319 341 365 391 415 442 470 499 Table 5 Cooling Performance AC Models 80 DB 67 WB Deg Return Air Air Temperature Entering Evaporator Coil Degree F COOLING...

Страница 20: ...82 90 102 108 118 129 36 27 32 38 46 50 56 71 79 91 96 106 115 48 34 38 43 50 54 61 76 84 97 103 113 124 60 36 41 46 55 58 65 80 87 99 104 113 123 24 Liquid 309 304 300 299 299 301 310 317 330 336 34...

Страница 21: ...507635 05 Page 21 of 22 Issue 2245 Wiring Diagrams Figure 8 AC Wiring Diagram...

Страница 22: ...Page 22 of 22 507635 05 Issue 2245 Figure 9 HP Wiring Diagram...

Отзывы: