background image

506860-03

Issue  1946

Page  17  of 27

Code

Diagnostic Codes / Status of Equipment

Action Required to Clear and Recover

E105

Device communication problem - No other devices on RS 

BUS (Communication system).

Equipment is unable to communicate. Indicates numerous 

message errors. In most cases, errors are related to electrical 

noise. Make sure high voltage power is separated from 

RSBus. Check for mis-wired and/or loose connections 

between the stat, indoor unit, and outdoor unit. Check for a 

high voltage source of noise close to the system. Fault clears 

after communication is restored.

E120

Unresponsive device (Communicating systems only).

Usually caused by delay in outdoor unit responding to indoor 

unit poling. Recycle power. Check all wiring connections. 

Cleared after unresponsive device responds to any inquiry.

E124

Active communicating thermostat signal missing for more 

than 3 minutes (Communicating systems only).

Equipment lost communication with the thermostat. Check 

four wiring connections, ohm wires, and cycle power at the 

thermostat. Alert stops all services and waits for heartbeat 

message from thermostat (subnet controller). Cleared after 

valid thermostat (subnet) message is received.

E125

Control failed self-check, internal error, failed hardware. 

Will restart if error recovers, Integrated control not 

communicating Covers hardware errors (flame sense 

circuit faults, pin shorts, etc).

Hardware problem on the control. Cycle power on control. 

Replace if problem prevents service and is persistent. Cleared 

300 seconds after fault recovered.

E126

Control internal communication problem.

Hardware problem on the control. Cycle power on control. 

Replace if problem prevents service and is persistent. Cleared 

300 seconds after fault recovered.

E131

Corrupted control parameters (Verify configuration of 

system) (Communicating systems only).

Reconfigure the system. Replace control if heating or cooling 

is not available. Only applicable in the communicating mode 

not in startup. Exit from Commissioning and Execute Se+ 

factory Default mode. Control will still operate on default 

parameter settings.

NOTE

Additional codes may be found in the Comfort Sync room thermostat manual.

Table 5. 7-Segment Alert and System Status Codes

7-Segment Alert and System Status Codes

Alert codes are displayed using the 7-segment display 

located on the outdoor control.

NOTE: 

System  fault  and  lockout  7-segment  display 

alarm  codes  take  precedence  over  system  status  codes 

(cooling, heating stages or defrost/dehumidification). Only 

the latest active fault or lockout alarm code, if present, will 

be displayed. If no fault or lockout codes are active, then 

system status codes are routinely displayed.

The 7-segment will display an abnormal condition (error 

code) when detected in the system. A list of the codes are 

shown in Table 5.

Resetting Alert Codes

Alert codes can be reset manually or automatically:

Manual Reset

Manual reset can be achieved by one of the following 

methods:

•  Disconnecting R wire from the main control’s R 

terminal.

• 

Turning the indoor unit off and back ON again. After 

power up, all existing codes will display for 60 seconds 

and then clear.

Automatic Reset

After an alert is detected, the main control continues to 

monitor the unit’s system and compressor operations. 

When/if conditions return to normal, the alert code is turned 

off automatically.

Содержание 4SHP16LS Series

Страница 1: ...local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or Canadian Electrical Code Canada Compliance should be determ...

Страница 2: ...ing parts 4 Handle refrigerant with caution refer to proper MSDS from refrigerant supplier 5 Use care when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living ar...

Страница 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Страница 4: ...24 3 8 3 4 36 3 8 7 8 48 3 8 7 8 60 3 8 1 1 8 For installations exceeding 50 refer to long line set guidelines Be extra careful with sharp bends Tubing can kink very easily and if this occurs the enti...

Страница 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Страница 6: ...hown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSE...

Страница 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Страница 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Страница 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Страница 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Страница 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Страница 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Страница 13: ...OR AIR HANDLER RSBus RSBus OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM THERMOSTAT COMFORT SYNCTM ENABLED HEAT PUMP RSBus OPTIONAL OUTDOOR AIR SENSOR OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM ENAB...

Страница 14: ...or varying lengths of line set refer to Table 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustme...

Страница 15: ...ocked out until power to the board is interrupted then re established or until the error is cleaned NOTE The control board ignores input from the low pressure switch terminals as follows During the TE...

Страница 16: ...m the Comfort Sync thermostat must be used The complete configuration of the outdoor unit is performed using the Comfort Sync thermostat For complete details on how to integrate this unit into a Comfo...

Страница 17: ...nication problem Hardware problem on the control Cycle power on control Replace if problem prevents service and is persistent Cleared 300 seconds after fault recovered E131 Corrupted control parameter...

Страница 18: ...r unit blower motor dirty filters or clogged refrigerant filter Confirm that the evaporator coil is clean The alarm clears after a power rest E412 The outdoor unit pressure is above the required limit...

Страница 19: ...ed by allowing the unit to run for 90 seconds before checking discharge sensor resistance If the discharge sensor resistance is not within range after 90 seconds the board will count one fault After 5...

Страница 20: ...Hz Idle Mode Decimal point blinks at 1 Hz 0 5 second on 0 5 second off Display OFF Soft Disabled Top and bottom horizontal line and decimal point blink at 1 Hz Soft Disabled Top and bottom horizontal...

Страница 21: ...650 pause A104 pause Outdoor Coil Temperature OCT Any time OCT is sensed in operating range value is displayed if unit is in diagnostic mode Following string is repeated if 2nd stage heat is active wi...

Страница 22: ...minutes if coil temperature remains below terminate temperature or by pushing button down for less than 2 seconds Enter A test mode Display will string active error codes E ambient A coil c and disch...

Страница 23: ...g procedure must be repeated Table 9 Configuring Unit Capacity Display Code Procedure Solid Pt Release push button Allows user to select type and number of stages on outdoor unit IMPORTANT Field repla...

Страница 24: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Страница 25: ...t may engage auxiliary heat during the defrost cycle to satisfy a heating demand however the unit will run to normal operation at the conclusion of the defrost cycle In case of extended power outage I...

Страница 26: ...506860 03 Issue 1946 Page 26 of 27 4SHP16LS124 36 48 Wiring Diagrams...

Страница 27: ...506860 03 Issue 1946 Page 27 of 27 4SHP16LS160...

Отзывы: