# 48387H005

Manifold Gauge Set

Manifold gauge sets used with systems charged with
R410A refrigerant must be capable of handling the higher
system operating pressures. The gauges should be rated
for use with pressures 0 – 800 on the high side and a low
side of 30" vacuum to 250 psi with dampened speed to
500 psi. Gauge hoses must be rated for use at up to 800
psi of pressure with a 4000 psi burst rating.

Liquid and Suction Line Service Valves

The liquid line and suction line service valves and service
ports are used for leak testing, evacuating, charging, and
checking charge.

Each valve is equipped with a service port which has a
factory-installed Schrader valve (see Figure 12). A service
port cap protects the Schrader valve from contamination
and serves as the primary leak seal.

To Access the Schrader Port:

1. Remove the service port cap with an adjustable wrench.

2. Connect gauge to the service port.

3. When testing is completed, replace service port cap.

Tighten finger tight, then an additional 1/6 turn.

To Open Liquid or Suction Line Service Valve:

1. Remove stem cap with an adjustable wrench.

2. Use a service wrench with a hex-head extension to

back the stem out counterclockwise  as far as it will
go. Use a 3/16" hex head extension for liquid line
service valves and a 5/16" extension for suction line
service valves.

3. Replace the stem cap. Tighten finger tight, then

tighten an additional 1/6 turn.

To Close Liquid or Suction Line Service Valve:

1. Remove the stem cap with an adjustable wrench.

2. Use a service wrench with a hex-head extension to turn

the stem clockwise to seat the valve. Tighten firmly.

3. Replace the stem cap. Tighten finger tight, then

tighten an additional 1/6 turn.

Suction Line (Ball Type) Service Valve

Suction line (ball type) service valves function the same
way as the other valves; the difference is in the construc-
tion (see Figure 13).

The ball valve is equipped with a service port with a
factory-installed Schrader valve. A service port cap
protects the Schrader valve from contamination and
serves as the primary seal.

Leak Testing

After the line set has been connected to the indoor and
outdoor units, the line set connections and indoor unit
must be checked for leaks.

Refrigerant can be harmful if inhaled. Refrigerant
must always be used and recovered responsibly.
Incorrect or irresponsible use of refrigerant can
result in personal injury or death.

  WARNING

Figure 12

Service Valve

Valve Closed

Valve Open

Содержание 4SCU13LE Series

Страница 1: ...sk of electrical shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury...

Страница 2: ...e is shipped with the unit while the TXV expansion valve must be ordered separately from the manufacturer A filter drier approved for use with 410A is installed in the unit IMPORTANT This product has...

Страница 3: ...coil Installation Instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltage po...

Страница 4: ...a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line set and or indoor coil will be used to complete the system refer to this sect...

Страница 5: ...s to consider when placing and installing a high efficiency outdoor unit Placement Be aware that some localities are adopting sound ordi nances based on how noisy the unit is at the neighbor s home no...

Страница 6: ...por Line Figure 9 Refrigerant Line Sets Installing Vertical Runs new construction shown Outside Wall Wood Block Between Studs IMPORTANT Refrigerant lines must not contact wall Vapor Line Liquid Line W...

Страница 7: ...l be sure to empty all existing traps Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the thermal expansion valve reducing system performance and capacity...

Страница 8: ...ore removing the recovery machine When the low side system pressures reach 0 psig close the suction line valve Disconnect all power to the existing outdoor unit Refer to the gauges after shutdown to c...

Страница 9: ...the piston orifice and used teflon seal Insert nozzle end of the expansion valve along with a new teflon seal into the distributor and tighten to 20 30 ft lbs Use backup wrench on all wrench flats Ov...

Страница 10: ...wrench with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service v...

Страница 11: ...r coil 6 After a short period of time open a refrigerant port to make sure that an adequate amount of refrigerant has been added for detection refrigerant requirements will vary with lengths Check all...

Страница 12: ...ge hose from the cylinder Open the manifold gauge valves to release the nitrogen from the line set and indoor unit 8 Reconnect the manifold gauge to the vacuum pump turn the pump on and continue to ev...

Страница 13: ...tage must be within the range listed on the unit nameplate If not do not start equipment until the power company has been consulted and the voltage condition corrected 6 Set thermostat for cooling dem...

Страница 14: ...Table 6 to determine the saturation temperature for the liquid line pressure reading 4 Subtract the liquid line temperature from the satura tion temperature according to the chart to determine subcoo...

Страница 15: ...Minor variations in these pres sures may be expected due to differences in installa tions Significant differences could mean that the system is not properly charged or that a problem exists with some...

Страница 16: ...8 7 1 3 9 3 1 6 2 3 1 4 1 5 2 3 4 3 1 4 2 3 7 3 1 4 1 3 4 3 1 5 2 3 7 3 1 4 3 3 0 3 1 F 5 9 3 6 3 2 4 1 6 7 3 2 4 1 2 7 3 6 3 1 4 7 3 9 3 1 2 6 3 5 3 1 6 8 3 9 3 1 3 8 3 3 3 1 F 5 0 1 3 1 4 4 4 1 8 2...

Страница 17: ...for correct voltage at unit with unit operating 6 Check amp draw outdoor fan motor Unit nameplate _________ Actual _________ NOTE If owner complains of insufficient cooling the unit should be gauged a...

Страница 18: ...nician ________________________________________ Nameplate Voltage ______________ Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________ Maximum Fuse or Circuit Breaker...

Страница 19: ...L AND LOCAL CODES OUTDOOR FAN F C H 1 2 3 R S C C 2 3 1 EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 BLACK ORANGE B4 PURPLE K1 S4 S24 A4 C Y1 TO 24 VAC POWER SOURCE 20 VA MINI...

Страница 20: ...ade by the warrantor this warranty is in lieu of and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to assume for it any...

Отзывы: