It is important that the selected location for the equipment is suitable and 

can adequately accommodate the unit physical size, the unit weight and 

has safe and suitable access for correct operation and future maintenance 

requirements.

Location of Equipment

Minimum Access Requirements 

for Maintenance

• 

The unit must be mounted so that sufficient space is 

allowed for installation and service access.

• 

Maintenance personnel need to gain access to all 

parts of the unit and be able to remove components 

such as fans and filters via access doors as required.

• 

Unless otherwise specified the following minimum 

access should be available:

• 

800mm clearance for electrical connections

• 

1200mm for all access doors on the unit or if no 

access door is provided 1200mm from the front of the 

unit. Be very mindful that internal filters need to be 

accessed regularly for cleaning.

• 

Every proposed installation must be subject to 

an engineered design by a mechanical services 

consultant. Armcor Air Solutions is not responsible 

for installation of equipment in situations for which 

the equipment was not designed or specified.

Noise Levels

• 

Do not locate equipment adjacent to sleeping 

quarters unless background noise levels have been 

checked and permitted by the appropriate authority.

• 

It is recommended that rubber supporting or 

vibration absorbing pads be used to support the unit 

to minimise any vibration being transmitted into the 

building structure. We recommend waffle pad to be 

used under the base frame and flexible couplings be 

fitted to the supply and return ducts to reduce any 

vibration transfer.

Fresh Air Inlet and Exhaust Air 

Outlet

• 

The location of the fresh air inlets must adhere to the 

Australian Standards 1668.2.

• 

The fresh air intake should be positioned clear of 

any objects which could obstruct the airflow and be 

a minimum distance of 6 metres from any exhaust 

discharge ducts from this unit or any other adjacent 

equipment. Refer to Australian Standards AS 1668.2.

• 

The fresh air inlet and exhaust air outlet should 

be fitted with a cowl or other suitable means of 

weatherproofing.

• 

The exhaust discharge should be directed away from 

any openable windows.

Drainage

Due to different moisture content levels of incoming 

fresh air, heat exchange equipment can be subject 

to some condensation. It is recommended that units 

located in ceiling spaces or plant rooms are installed 

with external drain trays under the complete unit.
Where an internal drain tray is fitted, the condensate 

drain outlet must be fitted with a ‘P-Trap’ and have a 

minimum fill of 20mm per metre length.

• 

Equipment should be installed with a positive fall 

to ensure water drains away freely through drain 

outlets. Drain lines must be as large as or larger than 

the fitting to which the line is being connected.

• 

All condensate drains must have a ‘P” Trap Fitted and 

have a minimum fall of 20mm per metre length.

• 

If drain lines are to be extended from the inside to 

the outside of the building, they must be extended 

beyond walls of the building to eliminate the 

possibility of damage caused by drain water running 

down the exterior surface of the building wall.

• 

When a drain is exposed to freezing temperatures or 

subject to the formation of condensation, the drain 

should be insulated.

IMPORTANT: ALL UNITS LOCATED INDOORS MUST HAVE 

DRAIN TRAYS UNDER THE COMPLETE UNIT.

  Armcor_XCM–Compact Multiflow ERV Installation and Operation Manual 2021                 5

Содержание XCM1225

Страница 1: ...Installation and Operation Manual XCM COMPACT MULTIFLOW ERV XCM125 XCM1225 M ADE A U STRALI A N Manufactured byArmcor M ADE A U STRALI A N Manufactured byArmcor...

Страница 2: ...Mains Power Supply and Fusing Equipment Layout 8 OPTIONS FOR EVERY INSTALLATION XCM With Centrifugal Fans General Maintenance 12 General Monthly Maintenance Schedules Guide to How Frequency According...

Страница 3: ...I sec Fan Filter Size mm Number of filters Weight kg Dimensions mm H x W x L XCM125P1 125 EC Plug 395 x 245 x 45 2 65 290 x 690 x 920 XCM225P1 225 EC Plug 395 x 395 x 45 2 80 440 x 690 x 920 XCM325C1...

Страница 4: ...overy and or air handling equipment Installing and servicing equipment can be hazardous due to electrical and mechanical components When working on equipment observe precautions in all literature tags...

Страница 5: ...nlet and Exhaust Air Outlet The location of the fresh air inlets must adhere to the Australian Standards 1668 2 The fresh air intake should be positioned clear of any objects which could obstruct the...

Страница 6: ...heck unit weight is within the safe tolerance of the working capacity of the crane Prepare for lifting with spreaders as you would do with lifting air conditioning equipment When lifting equipment nev...

Страница 7: ...commissioning IMPORTANT NEVER OPERATE A UNIT WITHOUT FILTERS FITTED TO THE RETURN AND FRESH AIR INTAKES WARRANTY IS VOID IF THE FILTERS ARE NOT FITTED AND REGULARLY CLEANED OR REPLACED Electrical Req...

Страница 8: ...conditioned area Exhaust Air Ducted to outside the building or into the roof space if adequate ventilation is available Fresh Air Use a fresh air cowl or grill to introduce fresh air Supply Air Connec...

Страница 9: ...ERY Exhaust Air Fresh Air Return Air Supply Air ENERGY RECOVERY Exhaust Air Fresh Air Supply Air Return Air ENERGY RECOVERY Exhaust Air Supply Air Fresh Air Return Air ENERGY RECOVERY Exhaust Air Fres...

Страница 10: ...ir ENERGY RECOVERY Exhaust Air Fresh Air Supply Air Return Air ENERGY RECOVERY Exhaust Air Supply Air Return Air Fresh Air ENERGY RECOVERY Exhaust Air Return Air Fresh Air Supply Air ENERGY RECOVERY E...

Страница 11: ...Take care not to damage the heat exchange modules Check the fan wiring is connected and will not interfere with fan operation Note On XCM625 and XCM925 the top panel of the unit will need to be remove...

Страница 12: ...to Usage is Established Disposable Corrugated Filters Standard disposable corrugated filters should last approximately one month in normal commercial use with 8 hours per day continuous operation or l...

Страница 13: ...ltage is available on all phases Check overload settings are correct if applicable Filters Check that both the fresh air and return air have adequate filters before starting unit Starting Unit Check F...

Страница 14: ...Air Flow L s Total Fresh Air Inlet Air Flow L s Total System external resistance Pa Measured downstream of fan outlets Estimate of Fresh Air Make Up or L s Electrical Supply Voltage Supply Fan Motor...

Страница 15: ...eplace as necessary Dirty contactor controls Clean and or replace Tripped Circuit Breaker Short circuit Trace and correct Earth leakage or over heating cables due to high load Meggar and replace as ne...

Страница 16: ...identifying a warranty claim Freight and travel changes for work performed or parts supplied outside of all capital cities in Australia Field wiring refrigerant pipe run between units the condensation...

Страница 17: ...Notes Armcor_XCM Compact Multiflow ERV Installation and Operation Manual 2021 17...

Страница 18: ...Notes 18 Armcor_XCM Compact Multiflow ERV Installation and Operation Manual 2021...

Страница 19: ...compact horizontal low profile heat recovery unit designed for installation within a roof space underfloor or in a plant room Read more here See our product brochure Armcor_XCM Compact Multiflow ERV...

Страница 20: ...Fresh Air Indoors For more information W armcor com au E sales armcor com au P 03 8301 9200 109 111 Northcorp Blvd Broadmeadows Vic 3047...

Отзывы: