Charging the battery 

When the batteries are not fully charged, the UPS will load them and the display charging indicator every 
time the device is connected to a power source. A full battery charge takes an average of more than 12 
hours. Backup time is reduced until the battery is fully charged. 

4.

 

Alarm 

4.1

 

The importance of sound signals 

While in use, the device, may send adequate signals depending on the current status of the device, battery, 
or  operating  mode.  Table  below  contains  information  about  sound  signals  and  the  reasons  for  its 
occurrence. 

Table of sound signals and their corresponding meaning

 

The device beeps every 8 seconds 

UPS switched to battery mode 

The device beeps every second 

Remaining backup time is shorter than 1 minute  

The device emits a constant beeping 

UPS is overloaded 

5.

 

Troubleshooting 

5.1

 

General information 

Troubleshooting card covers most of the problems that can occur during normal use of the device. If the 
UPS  is  not  working  properly,  please  refer  to  the  following  steps  and  find  possible  causes  and  solutions 
before contacting technical support. 

5.2

 

Preliminary proceedings 

Before checking the potential problems with the device check if: 

1)

 

UPS is correctly connected to the power output outlet; 

2)

 

The voltage across the line is stated in the specification; 

3)

 

The fuse or circuit protection device on the rear panel is open. 

5.3

 

Troubleshooting table 

Troubleshooting table 

Symptom 

Possible reason 

Possible solution 

UPS cannot be turned on 

UPS is not connected to the mains and 

is overloaded 

Plug the UPS to the mains and remove 

the load 

Input fuse is turned off 

Reset the fuse (press it again), remove 

some of the load or check that the load 

does not have a short circuit or is 

damaged 

The voltage input is too low 

Check if the power supply voltage is 

too low 

UPS malfunction 

Send the device to the local service for 

repair purposes. 

Red LED light is constantly glowing and 

UPS beeps every 8 seconds 

UPS switches to battery mode, despite 

the current power 

 Promptly save data and turn off the 

devices connected to the UPS 

Red LED light is constantly glowing and 

UPS beeps every second 

Remaining backup time is shorter than 

1 minute 

Turn off the operating system and 

charge the UPS again 

Yellow LED light is flashing and UPS 

emits a constant beeping 

UPS is overloaded. For protection 

purposes, it has been switched off 

Remove the load, which may cause the 

inclusion of security 

 
 
 

 

 

Содержание Home 1000E

Страница 1: ...ANUAL SERIA HOME HOME SERIES HOME INSTRUKCJA OBS UGI AWARYJNEGO SYSTEMU ZASILANIA UNINTERRUPTED POWER SUPPLY MANUAL LINE INTERACTIVE UPS ARMAC HOME 650E ARMAC HOME 850E ARMAC HOME 1000E ARMAC HOME 150...

Страница 2: ...nie baterii w trybie wy czonym offline 7 2 2 4 Ochrona przed przeci eniem 7 2 2 5 Ochrona przed wyczerpaniem baterii 7 2 2 6 Automatyczny test podczas uruchomienia urz dzenia 7 2 2 7 Funkcja zimnego s...

Страница 3: ...ami posiadaj cymi silnik elektryczny b d grza k Pod czaj c wymienione powy ej produkty do urz dzenia ryzykujesz ich uszkodzeniem Systemu UPS nie nale y u ywa w systemach podtrzymywania ycia lub innych...

Страница 4: ...cz dop yw zasilania sieciowego oraz zawiadom stra po arn o zaistnia ej sytuacji dzwoni c pod numer stra y obowi zuj cy w kraju w kt rym przebywasz NIGDY nie dopu do sytuacji w kt rej mog yby wyst pi...

Страница 5: ...z wentylacja Nie nale y instalowa i przechowywa systemu zasilania awaryjnego w miejscach w kt rych obecna jest stoj ca albo bie ca woda lub jakiekolwiek inne p ynne substancje Nie nale y instalowa ani...

Страница 6: ...TWOJE R D O ENERGII 6 INSTRUKCJA OBS UGI SERIA HOME PL EN RU 2 UPS 2 1 Przyk adowy wygl d urz dzenia...

Страница 7: ...czeg ln ostro no podczas od czania zasilania UPS a od gniazda zasilania sieciowego AC z powodu wyst powania napi cia podczas adowania baterii przez urz dzenie 2 2 4 Ochrona przed przeci eniem W czasie...

Страница 8: ...nia sieciowego AC 4 Dioda LED informuj ca e urz dzenie jest przeci one 5 Port USB 6 Port RJ 11 RJ 45 7 Bezpiecznik 8 Wej ciowy kabel zasilaj cy Wej ciowe gniazdo zasilaj ce IEC C14 9 Wyj ciowe gniazda...

Страница 9: ...sekundy UPS zostanie wy czony po d ugim sygnale d wi kowym 2 7 Tryby pracy 2 7 1 Zasilanie sieciowe AC Podczas dzia ania UPS w trybie zasilania sieciowego AC zielony wska nik LED b dzie nieustannie wi...

Страница 10: ...k i rozwi zania przed skontaktowaniem si z pomoc techniczn 5 2 Post powanie wst pne Przed przyst pieniem do sprawdzania ewentualnych problem w z urz dzeniem sprawd czy 1 UPS jest prawid owo pod czony...

Страница 11: ...zy komputerem a urz dzeniem Kliknij na ni dwukrotnie Pojawi si nowe okno w kt rym mo esz komunikowa si z UPS em oraz zarz dza jego ustawieniami 7 Specyfikacja Model HOME 650 HOME 850 HOME 1000 HOME 15...

Страница 12: ...charging in offline mode 17 2 2 4 Overload protection 17 2 2 5 Battery exhaustion protection 17 2 2 6 Automatic test during the device launch 17 2 2 7 Cold start feature 17 2 3 The importance of UPS b...

Страница 13: ...uts them at risk of damage UPS system should not be used in any life support systems or other relevant devices critical to your health 1 3 General safety precautions Use the device does not require sp...

Страница 14: ...ributor are not responsible for any damages resulting from improper usage and handling of the UPS not in accordance with these instructions 1 4 Personal safety precautions In case of required maintena...

Страница 15: ...re there is excessive humidity Remember to avoid exposure device to direct sunlight or direct heat sources Place the UPS on a stable dry surface in a well ventilated place Leave at least 100 mm of fre...

Страница 16: ...YOUR SOURCE OF ENERGY 16 MANUAL HOME SERIES PL EN RU 2 UPS 2 1 Sample device appearance...

Страница 17: ...tions when disconnecting the UPS from the mains AC outlet because of the voltage while the device is charging the battery 2 2 4 Overload protection While the UPS is overloaded during its operation and...

Страница 18: ...ly mode AC 4 LED Light indicating that the device is overloaded 5 USB Port 6 RJ 11 RJ 45 Port 7 Fuse 8 Input power cable Input power supply socket IEC C14 9 Power output sockets French type E schuko F...

Страница 19: ...und signal 2 7 Operating modes 2 7 1 Power supply AC During UPS operation in AC power mode AC the green LED will continuously glow indicating the normal operation of the UPS When the load level reache...

Страница 20: ...support 5 2 Preliminary proceedings Before checking the potential problems with the device check if 1 UPS is correctly connected to the power output outlet 2 The voltage across the line is stated in...

Страница 21: ...active connection between the computer and the device Click on it twice A new window will appear where you can communicate with the UPS and manage its settings 7 Technical specification Model HOME 650...

Страница 22: ...6 25 1 7 25 1 8 25 1 9 25 2 26 2 1 26 2 2 27 2 2 1 27 2 2 2 27 2 2 3 offline 27 2 2 4 27 2 2 5 27 2 2 6 27 2 2 7 27 2 3 28 2 4 29 2 5 29 2 6 29 2 6 1 29 2 6 2 29 2 7 29 2 7 1 AC 29 2 7 2 DC 29 3 29 3...

Страница 23: ...23 HOME PL EN RU 1 1 1 ARMAC HOME 650E HOME 850E HOME 1000E HOME 1500E HOME 650F HOME 850F HOME 1000F HOME 1500F 1 2 LED LCD 1 3 VDE CE...

Страница 24: ...24 HOME PL EN RU ON 24 1 4 o o...

Страница 25: ...25 HOME PL EN RU 15 1 5 1 6 1 7 1 8 100 1 9 CE www armac pl...

Страница 26: ...26 HOME PL EN RU 2 2 1...

Страница 27: ...27 HOME PL EN RU 2 2 2 2 1 2 2 2 INFO 2 2 3 offline 2 2 4 10 2 6 1 2 2 5 2 2 6 2 2 7 AC 2 6 1...

Страница 28: ...2 DC 3 AC 4 5 USB 6 RJ 11 RJ 45 7 8 14 9 schuko F 650 850 1000 1500 4 Backup Normal Overload 5 1 5 2 5 3 5 4 5 5 5 6 5 8 5 7 5 9 5 5 5 6 5 8 5 7 5 9 5 5 5 6 5 7 5 8 5 9 BREAKER 250V 6A INPUT 220V 50H...

Страница 29: ...29 HOME PL EN RU 2 4 3 INFO 2 5 AC 2 6 2 6 1 ON OFF 2 6 2 1 AC ON OFF 3 2 DC ON OFF 3 2 7 2 7 1 AC 100 LED 2 7 2 DC DC LED 8 LED LED 3 3 1...

Страница 30: ...30 HOME PL EN RU 3 2 100 12 4 4 1 8 1 1 5 5 1 5 2 1 2 3...

Страница 31: ...31 HOME PL EN RU 5 3 LED 8 LED 1 1 LED 12 1 2 3 6 USB USB www armac pl...

Страница 32: ...E 1500 650 VA 850 VA 1000 VA 1500 VA 390 W 480 W 650 W 950 W 145 VAC 290 VAC 195 VAC 255 VAC 50 12 V 7 x 1 12 V 9 x 1 12 V 7 x 2 12 V 9 x 2 1 95 2 35 3 95 4 7 4 6 90 3 20 45 0 45 C 10 90 PowerManager...

Отзывы: