Aritech IU2055NC Скачать руководство пользователя страница 3

P/N 10-5106-501-55NC-01 • 19FEB19 

 

3 / 4 

Assembly 

Install the module into the protective housing as shown in 
Figure 1. Connecting cables should be fed through the cable 
entry hole at the rear of the protective housing before the 
module is fixed into place. 

Addressing 

Each module must be assigned an address from 1 to 128. Use 
the rotary dial marked 0 to 12 to set the tens and hundreds part 
of the address, and the rotary dial marked 0 to 9 for the 
remaining digits. See Figure 5 for example address settings. 

Note: 

To overcome the mechanical effects of shipping and 

storage, we recommend that you first rotate each dial counter-
clockwise (to the 0 position) and then clockwise (to the dial’s 
maximum position) before setting the required address. 

To change the address of a module that is operational: 

1.  Disconnect the module from the loop. 

Wait at least 5 seconds for the module to completely 
power down. 

2.  Change the address on the module using the rotary dials. 

3.  Connect the module to the loop. 

4.  Configure the device at its new address, and then remove 

the old device address at the panel. 

Configuration 

The module operation mode (standard or IS) is configured 
using jumpers J4 and J5, as shown in the table below. The 
default configuration is for standard operation (non-IS). 

 

Jumper 

Standard 

Intrinsically safe 

J4 

On 

Off 

J5 

Off 

On 

 

Caution: 

Always check the jumper configuration to ensure that 

it is correct for your installation type (standard or intrinsically 
safe). 

Wiring 

Standa

rd installation wiring (non-IS) 

Connect the module to the addressable loop using the COM1 
(negative) and COM2 (positive) inputs, as shown in Figure 2. 
COM1 and COM2 are polarity sensitive. 

For conventional zone output wiring for standard applications, 
see Figure 3. The conventional zone output requires a 

3.9 kΩ 

end-of-line resistor. 

Conventional loop impedance/loads for standard installation 
are shown in the table below. 

 

Short circuit 

< 40 Ω 

Fire 

130 

Ω to 760 Ω 

Fault 

1.1 kΩ to 1.4 kΩ 

Normal* 

2.1 kΩ to 4.5 kΩ 

Open circuit 

> 7.5 kΩ 

* Including all devices and the 3.9 kΩ EOL resistor. 

Intrinsically safe installation wiring 

Connect the module to the addressable loop using the COM1 
(negative) and COM2 (positive) inputs, as shown in Figure 2. 
COM1 and COM2 are polarity sensitive. 

For conventional zone output wiring for IS applications, see 
Figure 4. 

The conventional zone output requires a 3.9 kΩ end-

of-line resistor. 

Never install standard conventional detectors behind the IS 
barrier. 

Conventional loop impedance/loads for IS installation are 
shown in the table below. 

 

Short circuit 

< 26 Ω 

Fire 

250 Ω to 450 Ω 

Fault 

680 Ω to 1 kΩ 

Normal* 

1.6 kΩ to 4 kΩ 

Open circuit 

7 kΩ 

* Including all devices and the 3.9 

kΩ EOL resistor. 

Maintenance 

Basic maintenance consists of a yearly visual inspection. Do 
not modify internal wiring or circuitry. 

The wire impedance and threshold levels should also be 
checked as follows: 

• 

Change EOL resistor to 330 

Ω and check that the system 

reports an alarm. 

• 

Change EOL resistor to 0 

Ω and check that the system 

reports a fault. 

• 

Change EOL resistor to open and check that the system 
reports a fault. 

• 

Restore the EOL resistor to 

3.9 kΩ and check that the 

system operates normally. 

Specifications 

 

Loop operating voltage  

21 to 28 VDC 

Loop current consumption 
 

Standby 

 

Alarm 

 
< 15 mA 
< 40 mA 

Remote LED current 

3.6 mA 

Zone operating voltage (in 
standby) 

17.5 to 18.5 VDC 

Zone cable resistance 
 

Standard installation 

 

IS installation 

 
< 40 

Ω 

< 26 

Ω 

Zone end-of-line resistor 

3.

9 kΩ, 5%, 1/4W 

IP rating 

IP40 

Operating environment 
 

Operating temperature 

 

Storage temperature 

 

Relative humidity 

 
−10 to +55°C 

−20 to +60ºC 
10 to 95% noncondensing 

Weight 

325 g 

Dimensions 

175 × 124 × 51 mm 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание IU2055NC

Страница 1: ... 2019 UTC Fire Security All rights reserved 1 4 P N 10 5106 501 55NC 01 19FEB19 IU2055NC Conventional Zone Monitor Unit Installation Sheet EN 1 2 www acornfiresecurity com www acornfiresecurity com ...

Страница 2: ...wiring 1 Conventional zone output 2 GBX2000 barrier 3 Compatible conventional detector IS 4 3 9 kΩ end of line resistor Figure 5 Example address settings Installation Caution For general guidelines on system planning design installation commissioning use and maintenance refer to the EN 54 14 standard and local regulations See your control panel compatibility list for details of devices that can be...

Страница 3: ...nal zone output requires a 3 9 kΩ end of line resistor Conventional loop impedance loads for standard installation are shown in the table below Short circuit 40 Ω Fire 130 Ω to 760 Ω Fault 1 1 kΩ to 1 4 kΩ Normal 2 1 kΩ to 4 5 kΩ Open circuit 7 5 kΩ Including all devices and the 3 9 kΩ EOL resistor Intrinsically safe installation wiring Connect the module to the addressable loop using the COM1 neg...

Страница 4: ...EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see http www recyclethis info Contact information and product documentation For contact informati...

Отзывы: