IU2055NC Conventional Zone Monitor Unit Installation Sheet
EN
1
2
www.acornfiresecurity.com
Страница 1: ... 2019 UTC Fire Security All rights reserved 1 4 P N 10 5106 501 55NC 01 19FEB19 IU2055NC Conventional Zone Monitor Unit Installation Sheet EN 1 2 www acornfiresecurity com www acornfiresecurity com ...
Страница 2: ...wiring 1 Conventional zone output 2 GBX2000 barrier 3 Compatible conventional detector IS 4 3 9 kΩ end of line resistor Figure 5 Example address settings Installation Caution For general guidelines on system planning design installation commissioning use and maintenance refer to the EN 54 14 standard and local regulations See your control panel compatibility list for details of devices that can be...
Страница 3: ...nal zone output requires a 3 9 kΩ end of line resistor Conventional loop impedance loads for standard installation are shown in the table below Short circuit 40 Ω Fire 130 Ω to 760 Ω Fault 1 1 kΩ to 1 4 kΩ Normal 2 1 kΩ to 4 5 kΩ Open circuit 7 5 kΩ Including all devices and the 3 9 kΩ EOL resistor Intrinsically safe installation wiring Connect the module to the addressable loop using the COM1 neg...
Страница 4: ...EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see http www recyclethis info Contact information and product documentation For contact informati...