Sounder delay off times
(SET TIMES MENU, 4,
)
SOUNDER DELAY OFF Thu 07/12/00 10:39:52
Monday
:18:00
Friday
:18:00
Tuesday
:18:00
Saturday
:18:00
Wednesday
:18:00
Sunday
:18:00
Thursday
:18:00
Lnk
:none
0. . 9,
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Set Times Menu
Page 68
Select item to be changed
or 0..9 change data in item (Unlock memory!)
Confirm change
The time each day that the Sounder Delay is automatically switched from ON to OFF is
set in this menu if the link is set to None. The time for each day of the week can be
allocated.
Note
that the switching of the delay from OFF to ON is a manual only operation
using the Sounder Delay ON/OFF pushbutton with the keyswitch enabled.
If no automatic delay off operation is required, then the time 00h00 must be used, it is
ignored by the FP2000 fire panel. The Sounder Delay can also be manually switched off
at any time using the front panel delay ON/OFF pushbutton.
Link: If the link is set to Fire Brigade, then the Sounder Off times are set to 00h00 and the
Fire Brigade Off Times (
Page 71
) are used to control the Sounder Delay. This means that
one time set is used if both the Sounder and Fire Brigade Delays are to be switched off at
the same time. Link must be set to none in order to use the Sounder Off Times.
*See Output Delays, Page 70
Содержание FP2000
Страница 1: ...FP2000 Analogue addressable Fire Panel Reference Guide LKFP2503 Revision 6 1 January 2001 ...
Страница 2: ......
Страница 4: ......
Страница 19: ...Move to the next field in the display Move to the previous field in the display Increment Decrement ...
Страница 132: ...Mover cursor back one position Confirm end of text input ...
Страница 206: ......
Страница 207: ......
Страница 208: ......
Страница 209: ......