1X-F Series Quick Installation Guide
Страница 1: ...nual call point resistance 1 Mixed zone 100 Ω Manual zone 100 to 680 Ω 1 Resistance must be rated at 1 W min Inputs and outputs The function of inputs and outputs is defined by the operating mode Inputs EN 54 2 Remote reset Delays off EN 54 2 Evacuation Remote reset Delays off EN 54 2 Scandinavia Fire routing extended fire routing delay 1 Delays off BS 5839 1 Class change Delays off NBN S21 100 Re...
Страница 2: ...the previous configuration menu on the seven segment display 4 Scroll to the previous configuration value for the active menu on the seven segment display Enter Confirm a menu selection or a value selection entry The configuration controls are also used to enter the user level password The seven segment display is visible when the control panel cover is removed Seven segment display LED Indication...
Страница 3: ...stallation manual Display Operating mode Zone type 01 EN 54 2 Mixed 05 EN 54 2 Evacuation Mixed 07 EN 54 2 Scandinavia Mixed 11 BS 5839 1 1 Mixed 21 NBN S21 100 Odd zones Automatic Even zones Manual 31 NEN 2535 Odd zones Automatic Even zones Manual 1 Requires an active end of line device for zone termination Contact information For contact information see www utcfireandsecurity com Copyright 2011 ...