SOLARcomfort hot water heating systems should be installed in
compliance with the following standards and regulations.

Water Supply (Water Fittings) Regulations 1999 / www.wras.co.uk

These regulations (bye-laws in Scotland) ensure a good supply of
wholesome water and that only approved materials, pipes and fittings are
used to convey water.

These are statutory documents and take priority over all other regulations
and recommendations.  The installation of an unvented hot water storage
cylinder is classified as a “Controlled Service” and Regulation G3 applies.
To meet the requirements of the Regulations, installation of an unvented
system should be undertaken by a “competent installer”.

All installations of unvented hot water storage systems having a capacity
of more than 15 litres should be notified to the relevant Local Authority by
means of building notice or by the submission of full plans.  It is important
to note that it is a criminal offence to install an unvented hot water storage
system without notifying the Local Authority.  The installation of the unvented
cylinder and hot water system must comply with BS 6700 and the HSE
Legionella Code of Practice.

Current guidance notes do not cover the connection of a solar thermal
circuit to an unvented storage vessel (cylinder).  However, if guidance is
sought for compliance with current regulations the fundamental principle
is to provide a fail-safe means of shutting off the solar input to the heat
exchanger if the cylinder temperature should rise above the set temperature
of the cylinder’s energy cut out.  (See Note 1).

As with all unvented hot water systems, notification of intention to install
should be given to your local building control.

Option A.  A non self-resetting mechanical shut-off should be installed on
the solar primary flow to the cylinder.  The mechanical shut-off should be
suitable for use with a solar primary circuit (i.e. high temperature and glycol
resistant).  The mechanical shut-off should be integrated electrically with
the cylinder energy cut out/s and if necessary the solar circuit temperature
control, please refer to the solar controller manufacturer for further
information.

Option B.  Where the solar controller and hydraulic system demonstrate
that by no lesser means the requirement in Option A is satisfied by other
means; certification by an approvals body is required to demonstrate that
in the event of the stored water going over temperature, the heat input to
the cylinder is isolated by physical means and is non self-resetting.

These systems should be clearly identified with reference to the approvals
body.  (See Note 2).

Note 1 :  Whilst most solar cylinders use a coil type heat exchanger other
options such as external plate to plate devices, external annulars or ‘tank
in tank’ systems may be used but the same control options always apply.

Note 2 :  Current approved bodies include the British Board of Agrèment
(BBA), WRc-NSF Limited, or KIWA.

4.1

W

ATER

 R

EGULATIONS

4.2

B

UILDING

 R

EGULATIONS

4.3

G

ENERAL

 G

UIDANCE

Содержание AST 100

Страница 1: ...SOLARcomfort Solar Hot Water Systems AST 100 Solar Controller Installation Commissioning and User Instructions LEAVE THESE INSTRUCTIONS WITH THE END USER Country of Destination GB IE...

Страница 2: ...IGATION 12 5 5 CONTROLLER SETTINGS 13 5 6 SYSTEM IMAGE 14 5 7 SYSTEM IMAGE ICONS 14 5 8 TOOL BAR 15 5 9 OPERATING MODE HND1 HND2 16 5 10 CONTROLLER SETTINGS 16 6 INSTALLATION 17 6 1 POSITIONING CONTRO...

Страница 3: ...nd conditions of guarantee on back page The complete SOLARcomfort solar water heating system is supplied in the following consignments 1 800201 Collector 1 per box 2 3107024 5 Roof Fittings Kit 1 card...

Страница 4: ...nder with the temperature of the solar collectors Whenever the solar collectors are hotter than the water within the cylinder the controller switches on the system s circulating pump The temperature d...

Страница 5: ...ow level fill point Ariston ITSI 210 300 twin coil cylinder Upper coil heated by boiler or other heat source Lower coil heated by solar energy AST 100 Controller Air vent PR Valve Solar system drain p...

Страница 6: ...ut by a competent qualified installer WARNING TYFOCOR LS HeatTransfer Fluid Although non toxic it should not be swallowed Refer to label on its container for storage and safety information A detailed...

Страница 7: ...C FUNCTIONS Temperature Differential Control Standard Operating Hours Counter Standard Energy Monitor Option ELECTRICAL Power Supply 210 240V Electromechanical Relay 250V Controller Mains Cable 1 0mm...

Страница 8: ...the Controller Item Description Qty 1 Controller 1 2 Sensor Collector 1 3 Sensor Cylinder Upper 1 4 Sensor Cylinder Lower 1 5 Spare Fuse T4A 1 6 Cable Clips and screws 4 7 Fixing Screws 2 8 Wall Plug...

Страница 9: ...provide a fail safe means of shutting off the solar input to the heat exchanger if the cylinder temperature should rise above the set temperature of the cylinder s energy cut out See Note 1 As with a...

Страница 10: ...5 www communities gov uk Control of Substances Hazardous to Health Regulations COSHH 1994 www hse gov uk Further details available from www hse gov uk Health Safety At Work Act HSW 1974 Work at Height...

Страница 11: ...linders IP13 93 Heating systems in buildings design for water based heating systems PrEN 12828 Building log books GPG 348 Solar heating CIBSE DBSP WGG Sun in Action II ESTIF Sun in Action II Minimisin...

Страница 12: ...only Typical operating display for standard system The cylinder can be either a twin coil or a single coil buffer type controlled by AST 100 Controller Arr 1 default Arr 2 5 OPERATION FUNCTIONS Typica...

Страница 13: ...lue Displays the current set value for the menu option selected When is also displayed it indicates that the value can be changed or set to zero using the set button refer to Section 5 5 IMPORTANT Men...

Страница 14: ...can be changed or reset will also be displayed TO CHANGE A VALUE 2 Press and hold set button until flashes 3 The current setting will be displayed Record current value so value is not forgotten Press...

Страница 15: ...s when TSTL is selected Lower cylinder temperature S3 flashes when TSTU is selected Upper cylinder temperature When icons flash rapidly it indicates a fault with the relevant sensor or that the sensor...

Страница 16: ...u f e z e e r f i t n A r O R F C e r u t a r e p m e t e z e e r f i t n a t e s w o l e b s i p m e t g n i h s a l F e i e v i t c a n w o d t u h s y t i r u c e s r o t c e l l o C d e d e e c x...

Страница 17: ...il stops flashing The new value will now be saved TO RESET A VALUE 2 Press and hold set button until flashes the value will be reset to 0 3 To confirm press again until it stops flashing To interrupt...

Страница 18: ...l length and may require terminal boxes and extra cable lengths to make connections The controller should be positioned so that it is inaccessible to children and cannot be tampered with 6 1 POSITIONI...

Страница 19: ...T The mains supply cable must be separated from the sensor cables by a minimum of 15mm ELECTROMECHANICAL RELAYS The SOLARcomfort controller incorporates two standard electromechanical relays which hav...

Страница 20: ...S2 Lower Sensor S1 Collector Sensor Collector Collector S4 Energy Monitoring Sensor option BS 1383 A kite marked Domestic Plug fused 5A or Double Pole Isolating Switch fused 5A as shown Cylinder Manu...

Страница 21: ...Collector Sensor Collector Collector FUSE 5A Mains Supply 220 240V BS 1383 A kite marked Domestic Plug fused 5A or Double Pole Isolating Switch fused 5A as shown R1 2 1 A 220 240V R2 2 1 A 220 240V 1...

Страница 22: ...ller is powered up the default setting will be for a standard system Arr 1 Setting Arr 1 or Arr 2 determines which set of options are available on the display see tables 7 2 and 7 3 Arr 1 or Arr 2 mus...

Страница 23: ...d Off by AHF see 7 5 20 7 5 21 When Arr 2 is selected extreme care must be taken to ensure the auxiliary heat source only operates when it will not adversely affect the cylinder temperature prior to a...

Страница 24: ...e l l o C m u m i x a M e r u t a r e p m e T r o t c e l l o C m u m i x a M e r u t a r e p m e T r o t c e l l o C m u m i x a M e r u t a r e p m e T r o t c e l l o C m u m i x a M e r u t a r e...

Страница 25: ...m e t s y S g n i l o o C m e t s y S r o t c e l l o C r o t c e l l o C r o t c e l l o C r o t c e l l o C r o t c e l l o C N O r o F F O F F O 3 5 7 X M C g n i l o o C m e t s y S g n i l o o C...

Страница 26: ...mperature Range 40 C to 250 C Display Only S3 is displayed when Arr 1 is set TSTU is displayed when Arr 2 is set Temperature of the cylinder as detected by upper cylinder sensor S3 Only displayed when...

Страница 27: ...is set to ON and a sensor S4 is connected to the collector return pipework The heat quantity transported is determined from 1 The flow volume as set by FMAX 2 The flow temperature of the collector as...

Страница 28: ...EAFTER 7 5 2 DT O Solar Pump Switch ON Temperature Differential Range 1 0K to 20 0K Default 6 0K The collector temperature as detected by S1 minus the cylinder temperature as detected by S2 equals the...

Страница 29: ...rature rises to the set CMX value the solar pump remains active R1 On until the set CMX value is under run again The cylinder temperature may continue to rise above the S MX value up to 95 C the cylin...

Страница 30: ...ing does increase the cylinder temperature however it will only rise up to 95 C the cylinder emergency shut down temperature at which point the pump will be switched Off R1 Off In the evening the pump...

Страница 31: ...ncentration of Antifreeze Range 20 to 70 Default 45 MED is only displayed when OHQM is set to On and MEDT is set to 1 Propylene glycol or 2 Ethylene Set value to the dilution of the antifreeze used in...

Страница 32: ...rr 2 is set 7 5 21 AHF R2 Thermostat Switch Off Temperatures AHF Range 0 to 95 C Default 40 C AHF is only available when Arr 2 is set AHO and AHF R2 can be used in two ways Normal Systems To switch On...

Страница 33: ...7 9 0 1 7 1 1 1 6 3 1 1 5 5 1 1 5 7 1 1 4 9 1 1 C 5 5 0 6 5 6 0 7 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 3 1 2 1 2 3 2 1 2 5 2 1 1 7 2 1 0 9 2 1 9 0 3 1 8 2 3 1 7 4 3 1 6 6 3 1 5 8 3 1 4 0 4 1 3...

Страница 34: ...O Is the collector sensor correctly fitted located Set Collector Temperature Monitoring Function OTC to On YES NO YES The collector temperature increases considerably more than the cylinder temperatur...

Страница 35: ...d the non return valve for 1 night Does cylinder still lose heat NO YES Use circulating pump with timer YES NO Check non return valve Does the system have high gravitation head YES NO A B A B Has the...

Страница 36: ...through menu options on the display Set Button Use to zero menu hour counters and energy monitor Menu Option Displays the option selected using the forward and backward buttons Value Displays the curr...

Страница 37: ...will be reset to 0 3 To confirm press set again until it stops flashing To interrupt reset procedure do not press any button for about 5 seconds and the controller option will return to previous sett...

Страница 38: ...nufacturer s instructions 2 Your installer does not complete the necessary commissioning process and procedure as detailed in the Installation and Operating Instruction manuals 3 Your appliance is not...

Отзывы: