48
GB
WARNING:
- Before carrying out any work, make sure that the units have been disconnected from the electricity supply.
- Make sure the systems to which the appliance should be connected comply with current applicable standards.
CHECKS WITHOUT THE USE OF TOOLS OR INSTRUMENTS
Operation in Cooling mode - Visual checks on the Internal Unit
Problem
Check
Action
1
- Frost forms on the Internal Unit heat
exchanger.
1.A
- Frost only at the bottom of the heat
exchanger: gas leak.
1.B
- Frost covers the entire heat ex-
changer: the air fi lter is clogged.
The room temperature is low
(
<
20°C).
· Find the leak and recharge.
· Clean the air fi lter.
Unplug the appliance and switch off
the dedicated switch before cleaning
(risk of electrocution).
· Check the room temp.
2
- No condensation forms.
2.A
- If the Internal Unit heat exchang-
er remains dry and the electricity
consumption is much lower than
the rated value, then there is a
leak.
· Find the leak.
· Replace the heat exchanger.
3
- The compressor runs but there is
little cooling.
3.A
- The External Unit heat exchanger
is clogged or covered: you do not
have a good heat exchange.
3.B
- The fl aps on the External Unit heat
exchanger are bent.
· Clean the External Unit heat exchang-
er.
· Straighten the fl aps on the external
heat exchanger.
4
- The air temperature is low, but there
is little cooling.
4.A
- The Internal Unit fi lter is clogged.
4.B
- The air recirculates in the Internal
Unit.
4.C
- The machine has not been sized
correctly or is overloaded e.g.: heat
sources, overcrowding,...).
· Clean the fi lter.
· Encourage the free circulation of air.
· Replace the appliance or remove the
overload.
5
- The compressor does not start.
5.A
- The compressor is very hot: heat
protection.
· Wait for the temperature to drop.
6
- The appliance comes to a stop after a
few minutes of operation.
6.A
- The internal unit fan is broken.
· Replace the motor.
· Only use original spare parts.
TROUBLESHOOTING - electrics
Problem
Check
Action
1
- The appliance gives no sign of life (no
LEDs lit, no beeps sounded), not even
when you press the ON-OFF button
on the internal unit.
1.A
- Check whether there has been a
power failure.
1.B
- Check whether the plug is inserted
fully in the socket in the wall.
1.C
-
Check whether the automatic
switch has blown.
1.D
-
Check whether the selector has
been set to stop.
· Restore the power supply and the cor-
rect connections.
· Plug the appliance in fully.
· Reset the automatic switch.
· Set the selector to another function.
2
- The remote control does not work or
only works from a short distance.
2.A
- Check whether the batteries are
low.
2.B
- Check whether there are any ob-
stacles (curtains or ornaments)
between the remote control and the
air conditioning unit.
2.C
- Check whether the distance be-
tween the remote control and the
unit is too far.
· Replace the batteries.
· Remove all obstacles.
· Move closer to the air conditioning unit.