LIMITED WARRANTY
This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty
claim online at www.intermatic.com. This warranty is made by: Intermatic Incorporated, Customer Service, 1950 Innovation Way Suite 300,
Libertyville, IL 60048. For warranty service go to: www.intermatic.com or call 815-675-7000.
For complete information on Intermatic products, literature and Contractors Guides visit www.intermatic.com.
158--02100REF
SWITCH INTERFACE
COVERAGE AREA
WIRING DIAGRAM
120-277 VAC
Power
Source
White
Black
Green
Neutral/Line 2
Line
ALC-DT
-BT
-WH
Wire
Description
White
Connects to Neutral/Line 2 from Power Source
Black
Connects to Line from Power Source
Green
Connects to ground
NOTE:
To be installed in single- or double-gang applications with 2-1/2” minimum depth.
Please consult a qualified electrician for specific wiring details.
(ft)
(ft)
PIR coverage
Ultrasonic coverage
TOP VIEW
(ft)
0
5
10
20
15
25
30
35
40
45
SIDE VIEW
0
5
10
20
15
5
10
15
20
0
3
6
9
18
BLUE LED
GREEN LED
RED LED
RESET
SWITCH
SHOWN WITHOUT
COVER AND LENSE
TROUBLESHOOTING
Symptom
During installation, the ARISTA Mobile App can’t find the sensor when scanning
for devices in the area
Verify power is supplied to the sensor. Make sure the Blue LED is blinking
slowly. If not, the sensor could already be provisioned into another area. If this
is correct, factory reset the device by pressing the reset button for more than
10 seconds. Make sure you are within range of the sensor
Sensor is energizing the lights without motion being detected in the space
Verify zone configuration using the ARISTA Mobile App is correct. Sensitivity
may be set too high. Using the ARISTA Mobile App, lower the sensors
sensitivity setting.
Sensor doesn’t detect motion when person enters the space
Verify power is supplied to the sensor. If Blue LED is blinking slow, the sensor
hasn’t been provisioned into the zone using the ARISTA Mobile App and will
not operate properly. Verify the sensor is detecting motion by walking by the
sensor and verifying the Green LED blinks briefly. Sensitivity setting may be set
too low. Using the ARISTA Mobile App, increase the sensors sensitivity setting.
Verify sensor configuration (i.e. – time delay). Make certain zone configuration
is set to Occupancy and not Vacancy. Change mounting location.
Sensor’s Red LED is on solid
Replace Sensor
Sensor is de-energizing the lights while still in the space
Sensitivity setting may be set too low. Using the ARISTA Mobile App, increase
the sensors sensitivity setting. Change mounting location.
Sensor leaves the lights energized after having left the space
Verify sensor configuration (i.e. – time delay).