17
Table 5 - Typical max buffer time with Aris
Power Battery Boxes BBX Series, 24 V
Load
Current
(A)
Minutes
BBX012
024
1.2 Ah
BBX034
024
3.4 Ah
BBX07
2024
7.2 Ah
1.5
20
60
200
3
8
30
120
5
3
15
55
7.5
2
10
30
10
NA
7
20
15
NA
NA
9
20
NA
NA
7
Load
Current
(A)
Minutes
BBX120024
12.0 Ah
100 Ah
1.5
400
NA
3
240
NA
5
100
NA
7.5
60
NA
10
45
1200
15
20
400
20
12
240
6.5
Fast Charge
To speed up the battery charging
process, the Fast Charge function can be
selected, hence applying the bulk
voltage on the battery. To enable this
function, the corresponding dip-switch n.
7 must be set at position B.
Figure 6.5 – Fast Charge setting
Factory setting is Fast Charge OFF. This
corresponds to dip switch n. 7 in position
A
6.6
Life test
The Life test function allows to perform a
diagnosis of the battery and to get
notified whether the battery is in a good
or a bad condition.
Figure 6.6 – Life Test Enable/Disable
Factory setting is Life Test OFF. This
corresponds to dip switch n. 8 in position
A.
6.7
Setting Power Supply
mode
This function allows the device to supply
energy while the battery is disconnected.
To enable this function, place the
corresponding dipswitch to the right.
Present on all DC-UPS and battery
charging devices but necessary and
factory configured on Battery Charging
devices only.
Figure 6.7 -Power supply mode setting
Factory setting is Power Supply OFF. This
corresponds to dip switch n. 8 in position
A.
Содержание DCU150M1224S
Страница 8: ...8 3 3 Dimensions Figure 3 2 Side and front views ...