2.2. Installation procedure 
 

1.

 

Install the valve as indicated by the arrow on the valve bonnet, indicating flow direction [

1

]. 

2.

 

In addition of the control valve it is recommended to install the following valves:  

 

Isolation valves upstream and downstream of the control valve [

8

]. 

 

Y-Strainer upstream of the control valve [

9

].  

 

 

 

3.

 

Close the outlet 

2

-way ball valve [

2

A]. 

4.

 

Turn on the water supply to the valve. 

5.

 

Check for leaks; tighten bolts & fittings, if necessary. 

6.

 

Mount the float valve [

5

] on the reservoir/tank at the desired level. 

7.

 

Connect the float valve [

5

C] to the outlet 

2

-way ball valve [

2

A] with the connecting tube [

7

]. 

8.

 

Close the 

isolation valves [

8

]. 

 

 

 

 

 

 

 

 

Содержание ELIPTIX R-30 Series

Страница 1: ...liptic shaped diaphragm that integrates well with a wide variety of regulating control pilots solenoids and control accessories They are compatibility designed for water level control flow control ele...

Страница 2: ...ol Valve 9 2 4 Initial Set up The ON OFF Application 10 3 OPERATION INSTRUCTIONS 11 4 MAINTENANCE 12 4 1 Periodic Inspection 12 4 2 Storing the valve 12 5 TROUBLESHOOTING 13 6 DISMANTLING AND ASSEMBLI...

Страница 3: ...ever whether caused by accessing and or relying upon this Disclaimer and or in any document enclosed hereto including without limitation any links procedures or materials A R I shall NOT assume any li...

Страница 4: ...iorwarning Make surethatallproducts outlet ports arenotdirectedtowardelectricalelements pumps orpeople 8 Always open and close valves slowly and gradually 9 Please note that the maximum working pressu...

Страница 5: ...lations set for handling this type of fluid 3 Before disconnecting the product from the system and before releasing the residual pressure do NOT loosen or unscrew the product bolts removeanyprotection...

Страница 6: ...ns 2 Make sure that all the tools ladders lifting devices etc used during the maintenance procedures are taken away from the product area and stored 3 Remove grease and fat material residues in order...

Страница 7: ...2 Before installing the valve flush the pipeline to remove scale dirt and other particles that might affect the valve performance 3 Carefully remove the valve from the shipping package Unload all valv...

Страница 8: ...tion valves upstream and downstream of the control valve 8 Y Strainer upstream of the control valve 9 3 Close the outlet 2 way ball valve 2A 4 Turn on the water supply to the valve 5 Check for leaks t...

Страница 9: ...5 Gradually open the downstream isolation valve 8A 6 For automatic operation of the level control valve open the 2 way ball valves 2 and 2A 7 To manually close the valve close the outlet 2 way ball v...

Страница 10: ...reservoir water level rises back to the pre set level the vertical float 5B floats with it As the float reach the upper stopper 5D the float valve 5C closes water from the upstream 2 way ball valve 2...

Страница 11: ...the valve close the outlet 2 way ball valve 2A and make sure that the inlet 2 way ball valve 2 is open 3 To manually open the valve close the inlet 2 way ball valve 2 and make sure that the outlet 2...

Страница 12: ...lly inspect the valve s diaphragm for any tears 2 Every 12 months inspect the valve s operation and clean the Finger Filter 3 Check the downstream pressure adjust if required 4 2 Storing the valve It...

Страница 13: ...r stopper 5E Valve does not close 1 The inlet 2 way ball valve 2 is closed 1 Check the Inlet 2 way ball valve position 2 1 Open the 2 way Inlet ball valve 2 2 The diaphragm is damaged 2 Check the Diap...

Страница 14: ...ing at the other 24 mm spanner open at one end and ring at the other 2 Release Pressure Make sure that the water supply to the valve is switched off release any residual pressure and isolate the valve...

Страница 15: ...Disassembling the valve 1 Using a 24mm spanner release the 4 bolts of the valve s bonnet in a diagonal manner A D 2 Un screw the bonnet s bolts E F and remove the bonnet from the valve s body G H 1 1...

Страница 16: ...R 30 Y 3 Remove the valve s spring I J 4 Remove the valve s diaphragm K L 3 3 4 4...

Страница 17: ...Cleaning the Finger Filter 1 Disassemble and clean the finger filter using a 20mm spanner release the upstream 2 way manual valve A B Then using a 19mm spanner release the finger filter and clean it C...

Страница 18: ...d tightened in all directions parallel to the valve s body 6 6 Reassembling the Control loop 1 Make sure that all the control loop components are in good condition and clean 2 Clean the control tubing...

Страница 19: ...R 30 Y 7 DIMENSIONAL DRAWING...

Страница 20: ...le nor does this warranty extended to any consequential or incidental damages or expenses of any kind or nature regardless of the nature thereof including without limitation injury to persons or prope...

Отзывы: