Argus Security Taurus TW-MO-SB-01 Скачать руководство пользователя страница 2

• Refit the lid to the back box, using the supplied screws. 
• Put the QR code available in the box either on the system

map or on the dedicated pages at the end of translator 
or expander manual.

6

5

+

Unsupervised relay

switch output

WIRING EXAMPLE FOR THE RELAY SWITCH OUTPUT 

• Ensure the device connected to the unit is not drawing 

more than 2 A at 30V (no 220 VAC). Drawing too much 
current through the output relay or connecting mains
voltage could possibly damage the unit and void warranty.

Note: install a properly fire rated cable (according 
to national code of practice) between the third-party 
device and the output module.

R

EOL

Supervised relay switch 

output (needs polarised load)

V

EXTERNAL

DEVICE

-     +

- +

-     +

- +

port B input

port A output

power supply

V

+

External

device

R

EOL

WIRING EXAMPLE FOR 100MA/12 VDC OR 50 MA/24 

VDC EXTERNAL DEVICE DRIVING CAPABILITY 

• The 10K

 R        resistor monitors whether the cable

has been damaged or the connection is no longer available.

• If you fail to install these resistors correctly the device will

not operate as intended. 

-     +

- +

R

EOL

R

EOL 

10 K

external

device

-     +

- +

EOL

R

EOL 

10 K

TW-MO-SB-01

WIRELESS BATTERY POWERED OUTPUT MODULE

QUICK START GUIDE

ARGUS SECURITY SRL, VIA DEL CANNETO, 14, 34015 MUGGIA, (TS), ITALY 
T: +39-040.23.96.411, E: [email protected], W: www.argussecurity.it