BASE INSTALLATION 

Fix the base to the wall with the provided screws (picture 4). 
 

DETECTOR PLACEMENT 

 
1)  Install the batteries cover. 
2)  Position the detector centrally on the base 
ensuring it is level. 
3)  Rotate clockwise applying gentle pressure. 
The detector will drop into its keyed location. 
4)  Continue to rotate clockwise a few degrees 
until the detector has fully engaged in the 
base. 
5)  When the detector is firmly engaged, check 
the alignment of the raised reference marks 
on the detector and on the base (picture 5). 
 

DETECTOR LOCKING 

To lock the detector to the base, screw in the provided security screw; screw entry is locat-
ed on the side of the detector’s base (picture 6). 
 

TAMPER DETECTION 

When the detector is detached from the base a tamper message event is sent to the control panel. 
 

TESTING 

 

Test this detector after installation. 

 
After each test reset the fire security system from the control panel, as per your control panel in-
structions. 
 

TEST MODES 

Test modes make the 

L-MC-SG 

more reactive to aerosol stimulus; two test mode types are  

provided: 
 
Type 1 Test Mode - triggered by a test magnet; persists for 1 minute. This mode makes the detector 
almost  instantaneously alarm agent reactive. 
 
Type 2 Test Mode - remotely triggered by the Wirelex program; persist for 30 minutes. This mode 
makes the detector as reactive to smoke as an optical smoke detector, simulating it. 
 

TEST 1 - MAGNET TEST 

 
1) Hold a suitable magnet in correspondence of the indicated area (picture 7) 
2) LED indicator will signal “Type 1 Test Mode”  
3) Apply again the magnet in correspondence of the indicated area (picture 7) 
4) LED indicator will signal “Alarm” 
 

TEST 2 - AEROSOL TEST 

 

Use only suitable aerosol testers supplied by approved manufacturers. 

 
1) Hold a suitable magnet in correspondence of the indicated area (picture 7) 
2) LED indicator will signal “Type 1 Test Mode” 
3) By following its specific instructions, apply the aerosol test device to the detector 
4) Wait a few seconds 
5) LED indicator will signal “Alarm” 
 

TEST 3 - AEROSOL TEST 
 
Use only suitable aerosol testers supplied by approved manufacturers. 

 
1) Remotely activate the detector’s green LED from the Wirelex program 
2) LED indicator will signal “Type 2 Test Mode” 
3) By following its specific instructions, apply the aerosol test device to the detector 
4) Wait a few seconds 
5) LED indicator will signal “Alarm” 
 

TEST 4 - HEAT TEST 

 

Use only suitable heat test devices from approved manufacturers. 

 
1) By following its specific instructions, apply the heat test device to the detector. 
2) Wait a few seconds. 
3) LED indicator will signal “Alarm”. 

Picture 5 

Dust  covers  DO  NOT  provide 
complete  protection  against 
contamination: 

detectors 

should  be  removed  before  construc-
tion, major re-decoration or other dust 
producing work is started. 
 
Dust covers MUST be removed before 
the system can be made operational. 

ARGUS SECURITY S.R.L.

 - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy 

www.argussecurity.it 

Picture 4 

Picture 6 

Picture 7 

MAINTENANCE - CLEANING 

 
1)  Remove the detector from its base. 
 
2)  Smoke  entry  areas  and  thermistor  area:  use  a  small, 
soft  bristle  brush  to  dislodge  any  obvious  contaminants 
such as insects, spider webs, hairs, etc. 
 
3)  Smoke  entry  areas  and  thermistor  area:  use  a  small 
vacuum tube or dry, clean, compressed air to suck up or 
blow any remaining small particles away. 
 
4)  Wipe the exterior housing of the detector with a clean, 
damp,  lint-free  cloth  to remove  any  surface  film  that  can 
later attract airborne contaminants. 
 
5)  Install the detector onto its base again. 
 
6)  Test the detector. 
 
 
 
 
 
 

MAINTENANCE - BATTERY REPLACEMENT 

 

When a low battery condition is indicated,  
both batteries must be changed altogether. 

 

During this procedure the linking switch must NOT  
be touched at all ! 

 
 
1)  Detach the detector from its base. 
 
2)  Extract the batteries cover. 
 
3)  Extract the batteries. 
 
4)  Insert the new batteries into their holders,  
 

oriented as per polarity marks. 

 
5)  Reinstall the batteries cover. 
 
6)  Reinstall the detector onto its base. 
 
7)  Test the detector. 
 

[email protected] 

L20-LMCXX-0001 (vA.7) 

AB 

Table 3 

TECHNICAL SPECIFICATIONS ** 

Communication range with the 
translator or expander 

200 m 

Open space 

Operating frequency 

868 MHz 

 

Operating frequency channels 

 

Radiated power 

≤ 14 dBm (25 mW) 

 

Batteries type* 

Type CR123A (3 Vdc) 

8.2 years life 

Parent expander’s check-up period 

60 seconds (default setting) 

 

Alarm threshold temperature. 
Class A1R ROR 

58 °C 

 

Alarm threshold temperature. 
Class B - high temperature  

78 °C 

 

Dimensions 

110 mm x 65 mm 

 

Weight 

190 g 

Base and batteries 
included 

IP rating  

40 

 

Max tolerated humidity 
(no condensing) 

95% RH 

 

Operating temperature range 

From –10 °C to +55 °C 

 

WARNINGS AND LIMITATIONS 

 
Our  devices  use  high  quality electronic  components  and  plastic  materials  that  are  highly  resistant to  environ-
mental deterioration. However, after 10 years of continuous operation, it is advisable to replace the devices in 
order to minimize the risk of reduced performance caused by external factors. Ensure that this device is only 
used with compatible control panels. Detection systems must be checked, serviced and maintained on a regular 
basis to confirm correct operation. Smoke detectors may respond differently to various kinds of smoke particles, 
thus application advice should be sought for special risks. Detectors cannot respond correctly if barriers exist 
between them and the fire location and may be affected by special environmental conditions. Refer to and follow 
national  codes  of  practice  and  other  internationally  recognized  fire  engineering  standards.  Appropriate  risk 
assessment should be carried out initially to determine correct design criteria and updated periodically. 
 

WARRANTY 

 
All devices are supplied with the benefit of a limited 3 year warranty relating to faulty materials or manufacturing 
defects, effective from the production date indicated on each product. This warranty is invalidated by mechani-
cal or electrical damage caused in the field by incorrect handling or usage. Product must be returned via your 
authorized supplier for repair or replacement together with full information on any problem identified. Full details 
on our warranty and product’s returns policy can be obtained upon request. 

 

ARGUS SECURITY S.R.L. 

Via del Canneto, 14 

34015 Muggia (TS) 

Italy 

 

16 

 

LI0110CPR 

EN 54-25:2008 
 
EN 54-5:2000 
Class A1R 
 
EN 54-7:2000+A1:2002+A2:2006 
 
CEA 4021:2003 
 
L-MC-SG 
 
For use in compatible fire 
detection and alarm system 

SMOKE SENSITIVITY (EN 54) 

Threshold level 

Wirelex setting 

Notes 

Level 1 

High 

 

Level 2 

Normal 

default 

Level 3 

Low 

 

THERMAL SENSITIVITY (EN 54) 

Detector Class 

Wirelex setting 

Notes 

A1R 

A1R 

default 

BS 

High temperature 

Non-approved 

NOTE OF THE DOCUMENT: 

Argus  Security  Srl    hereby  declares  that  this  detector  is  in  compliance  with  the  essential  requirements    and  
other relevant  provisions of Directive 1999/5/EC. A copy of the original Declaration of Conformity  
(Document: DoC LI01) is made available to the user on website: www.argussecurity.it 

Table 4 

Table 5 

* When a low battery condition is indicated, both batteries must be changed for new cells. 
   Lifespan of batteries indicated is subject to standard environmental conditions default  
   monitor settings and excellent link quality. 

**  Check  latest  version  of  document  TDS-LMCXX  for  further  data,  obtainable  from  your 
supplier. 