IMPORTANT POINTS ON SERVICE OPERATING SAFETY

 

Please follow these instructions carefully:

 

Unplug the unit to avoid any danger from electric shock before disassembling the unit for

 

repair.

 

If there is any sound of the refrigerant circulating when in operation, avoid touching the

 

cooling coils.

 

If you need to perform any welding or soldering, be sure you are in a well ventilated area.

 

Only a qualified professional should perform any welding on the unit.

When repairing the unit, the specifications listed in this manual must be strictly adhered

 

to when replacing any components.

 

When replacing any electrical components they should be factory approved units.

 

Be sure that any electrical components are properly wired and in place.

FLOW CHART FOR INSPECTING AND REPAIRING THE UNIT

 

Dehumidifier

doesn't work

Check if drain bucket

 

 water level switch

 

     is broken

 

Electricity shutdown

 Check fuses

 

on main switch

 Can not

dehumidify

Humidity switch

 

  is broken

 

Check if air filter

  is clogged

 

 Humidity switch is set

 

on continuous operation

 

Capacitors

 

are faulty

 

Compressor

doesn't work

Over load protector

 

      is faulty

 

Refrigerant

 is leaking

  Maintain

      &

 

repair system

Supply Nitrogen 15KG/CM2 from low

pressure side and locate the leakage

Use oxygen acetylene and 5% silver

    iron to fill cracks and holes

Pump vacuum for at

 least 15 minutes

  After filling with

refrigerant proceed

 

      to test run

- 1-

Содержание NARCISO 12

Страница 1: ... Widetech reserves the right to change this dehumidifier s casing circuit and parts without notice Important points on service and operating safety with a flow chart for inspection and repair 1 Troubleshooting 2 Appearance and and functions of this unit 3 Technical specifications 4 Refrigerator system and schematic wiring Diagrams 5 ...

Страница 2: ...cing any electrical components they should be factory approved units Be sure that any electrical components are properly wired and in place FLOW CHART FOR INSPECTING AND REPAIRING THE UNIT Dehumidifier doesn t work Check if drain bucket water level switch is broken Electricity shutdown Check fuses on main switch Can not dehumidify Humidity switch is broken Check if air filter is clogged Humidity s...

Страница 3: ...ter is dirty Repair or replace Clean filter Detect the leakage and fill with refrigerant Normal Move to level place or use blocks Tighten screws Normal it is the sound when the refrigerant is flowing Clean filter Can not dehumidify or the dehumidifcation volume is too low Refrigerant is leaking Low temp and humidity Uneven floor Loud noise and vibration Motor or compressor is loose Sound of flowin...

Страница 4: ...en the water tank is full the full tank lamp will light up the dehumidifier will stop operating immediately BUCKET FULL LAMP BUCKET FULL LAMP When the lamp lights up which means dehumidifier is operating RUNNING LAMP RUNNING LAMP When operating under low temperature for a short period the dehumidifier will starting defrost process the indicating lamp will light up DEFROST LAMP DEFROST LAMP Dehumid...

Страница 5: ...220 240V 50Hz Capacitor WATER TANK CAPACITY POWER INPUT W UNIT 12 at 30 C 80 RH WIRE SPECIFICATION A MODEL POWER INPUT EVAPORATOR CONDENSER RxSxFPIxW RxSxFPIxW REFRIGERANT CAPILLARY mm Mm Kg COMP O L P F V 260 1 13 41 2 PHP 206 16A 250V H05VV F VDE 3G0 75mm 405W 632H 290D 13 5 35D020 B1 AADM 1 06 233 LS 16D1 01 30 8 450 MRA12279 12095 R 134a g 150 5 2 4 1R8S21FPI x 12 7mm 2R8S19FPI x 25 4mm D2 2 x...

Страница 6: ...R COMPRESSOR ASS Y FAN MOTOR SCHEMATIC WIRING DIAGRAM PTC HEATER 5 REFRIGERATOR SYSTEM DIAGRAM AC CORD WHITE BLUE BLUE FUSE T6 3AL 250V BROWN CMP FAN MOTOR CAPACITOR BLACK WHITE HUMIDITY SWITCH SENSOR RUN LAMP FULL LAMP DEFROST LAMP D6951 630 ...

Отзывы: