(3) Malfunction of Insufficient Refrigerant protection F0
Clean the heat exchangers and remove
blockage of air inlet/outlet.
Insert the evaporator sensor tightly
Replace a main
board with the
same model.
Troubleshooting
for F0 malfunction
Check whether the
refrigerant is leaking?
Yes
No
Heat exchangers are
too dirty or the air inlet/outlet
is blocked.
Yes
Malfunction is
eliminated.
Yes
No
No
evaporator sensor is inserted
tightly?
Yes
Malfunction is
eliminated.
Yes
No
No
End