IMPORTANT!
Please read before installation

This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important  to install or
service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical  codes.
• Pay close attention to all warning and caution notices given in

this manual.

•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.

If necessary, get help

These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.

In case of improper installation

The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system and

then the wiring one; proceed in the reverse orden when removing
the units.

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing are

completed or reconnected and checked, to ensure the grounding.

• Highly dangerous electrical voltages are used in this system.

Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause

accidental injury and death

.

Ground the unit 

following local electrical codes.

• The Yellow/Green wire cannot be used for any connection

different from the ground connection.

• Connect all wiring tightly. Loose wiring may cause overheating

at connection points and a possible fire hazard.

• Do not allow wiring to touch the refrigerant tubing, compressor,

or any moving parts of the fan.

• Do not use multi-core cable when wiring the power supply and

control lines. Use separate cables for each type of line.

When transporting

Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.

When installing...
... In a ceiling or wall

Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.

... In a room

Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls
and floors.

... In moist or uneven locations

Use a raised concrete base to provide a solid level foundation for
the outdoor unit.
This prevents damage and abnormal vibrations.

... In area with strong winds

Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)

Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.

When connecting refrigerant tubing

• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare

and union tubes before connecting them;  screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.

• Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.

When servicing

• Turn the power OFF at the main power board  before opening

the unit to check or repair electrical parts and wiring.

• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no

metal scraps or bits of wiring have been left inside the unit being
serviced.

• Ventilate the room during the installation or testng the refrigeration

system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.

WARNING

CAUTION

WARNING

2

Содержание AE100SCL3

Страница 1: ...L3 AE100SCL3 AE764SCL3 AE125SCL3 0 8180 540 0 09 2008 SPLIT SYSTEM AIR CONDITIONER AE752SCL3 AE764SCL3 387007178 387007179 Product Code No 387007174 387007175 387007177 Model No AE726SCL AE735SCL AE752SCL Model No AE71SCL3 AE100SCL3 AE125SCL3 Product Code No 387007180 387007181 387007182 ...

Страница 2: ...ring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminium fins...

Страница 3: ...ons 13 2 3 Other Component specifications 21 3 DIMENSIONAL DATA 22 4 REFRIGERANT FLOW DIAGRAM 25 5 PERFORMANCE DATA 27 5 1 Performance Charts 27 5 2 Cooling Capacity 35 6 ELECTRICAL DATA 43 6 1 Electrical characteristics 43 6 2 Electric Wiring Diagram 46 6 3 System Wiring Diagram 50 Table of Contents 3 ...

Страница 4: ...1 OPERATING RANGE Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Cooling Maximum Minimum 43 C D B 15 C D B 32 C D B 23 C W B 19 C D B 14 C W B 4 ...

Страница 5: ...able tubing length at shipment m Refrigerant Narrow tube mm in tube diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 ...

Страница 6: ...shipment m Refrigerant Narrow tube mm in tube diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B For other INDOOR...

Страница 7: ... shipment m Refrigerant Narrow tube mm in tube diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B For other INDOO...

Страница 8: ...t shipment m Refrigerant Narrow tube mm in tube diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B For other INDO...

Страница 9: ...shipment m Refrigerant Narrow tube mm in tube diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B For other INDOOR...

Страница 10: ...hipment m Refrigerant Narrow tube mm in tube diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B For other INDOOR ...

Страница 11: ...nt m Refrigerant Narrow tube mm in tube diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B For other INDOOR UNITS...

Страница 12: ...ent m Refrigerant Narrow tube mm in tube diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B For other INDOOR UNIT...

Страница 13: ...h Nominal output W Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 30 700 MRA99901 9201 N A N A RB68A Freol Alpha 68M 350 C R 3 863 C S 3 309 External OLR T Rotary Hermetic 5PS102EAG01 400 Propeller 1 Ø 370 IB 966 501 1 6 865 1 5 450 21...

Страница 14: ...W Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE Acrylic baked on enamel finish Aluminium plate fin Copper tube 2 1 4 0 34 6 865 1 5 450 21 BRN WHT 242 4 WHT YEL 408 1 Thermal protector 120 5 400 Propeller 1 Ø 370 IB 966 501 1 Rotary H...

Страница 15: ...utput W Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 2 1 5 0 51 Acrylic baked on enamel finish 80 15 2 440 Aluminium plate fin Copper tube BRN WHT 98 5 WHT PNK 201 0 Thermal protector 130 5 1 Ø 400 KFG6 51SB5P 1 6 900 40 50 370 Prope...

Страница 16: ...tput W Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE Acrylic baked on enamel finish Aluminium plate fin Copper tube 2 1 5 0 51 130 5 80 15 2 440 40 BRN WHT 98 5 WHT PNK 201 0 Thermal protector Propeller 1 Ø 400 KFG6 51SB5P 1 6 900 N A...

Страница 17: ...output W Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 2 1 4 0 60 Acrylic baked on enamel finish N A 6 440 Aluminium plate fin Copper tube WHT PNK 50 7 WHT BRN 88 9 Thermal protector 130 5 1 Ø 460 Y7S623B54 1 4 760 60 N A Propeller V ...

Страница 18: ...put W Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE Rotary Hermetic 5JS330PBA21 2845 2895 FV50S 1130 U V 5 786 U W 5 954 V W 5 562 Internal Thermal protector N A N A Propeller 1 Ø 460 Y7S623B54 1 4 760 60 WHT PNK 50 7 WHT BRN 88 9 The...

Страница 19: ...Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE Rotary Hermetic 5JD420PAA02 3500 RB68A o Freol Alpha68M 1300 U V 3 478 U W 3 576 V W 3 344 Internal Thermal protector N A N A Propeller 1 Ø 460 Y7S623B54 1 4 760 60 WHT PNK 50 7 WHT BRN 88...

Страница 20: ...nal output W Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE Rotary Hermetic ZP67KCE TFD 5200 POE 1660 U V 2 5 U W 2 5 V W 2 5 Internal Thermal protector N A N A Propeller 1 Ø 460 Y7S623B54 1 4 760 60 WHT PNK 50 7 WHT BRN 88 9 Thermal p...

Страница 21: ... 10 Power relay compressor PR FINDER 65 31 Contact rating 30 A 250 V Coil supply 230 V 50 Hz Coil resistance 20 C Ω 7250 10 Negative Phase Relay Type Rating Contact Rating Operation Fan Speed Controller Type Factory setting Adjustable range 16 to 39bar RGE Z1L6 7DS CISE131 V AC 380 V 3 PHASE 50 Hz AC 250 V 8 A Positive phase ON Negative phase OFF HIGH LOW 28 5 C 1 LOW HIGH 31 C 1 YTB S383 30bar 21...

Страница 22: ...or Unit AE726SCL AE735SCL 700 540 15 470 4 ø12 holes 116 320 294 Air intake Air discharge 255 10 170 103 57 Narrow tube service valve ø6 35 1 4 Wide tube service valve ø9 52 3 8 ø12 7 1 2 7000 9000 BTU h 12000 BTU h Unit mm 22 ...

Страница 23: ... AE752SCL AE752SCL3 dimension mm Outdoor Unit AE764SCL3 AE71SCL3 dimension mm WIDE TUBE D 15 88 5 8 NARROW TUBE D 6 35 1 4 NARROW TUBE D 6 35 1 4 WIDE TUBE D 12 7 1 2 4 Ø12 for anchor bolt 4 Ø13 for anchor bolt 23 ...

Страница 24: ...Outdoor Unit AE100SCL3 AE125SCL3 dimension mm 24 ...

Страница 25: ...door Unit AW726CL AW735CL AW752CL AW764CL AS71CL Outdoor Unit AE726SCL AE735SCL AE752SCL AE752SCL3 AE764SCL3 AE71SCL3 Indoor Unit AS100CL AS125CL Outdoor Unit AE100SCL3 AE125SCL3 Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 25 ...

Страница 26: ... cold To prevent heat loss and wet floors due to dripping of condensation both tubes must be well insulated with a proper insulation material The thickness of the insulation should be a min 8mm CAUTION After a tube has been insulated never try to bend it into a narrow curve because it can cause the tube to break or crack 26 ...

Страница 27: ...tion Data referred to AW726CL 2 6 2 8 3 0 3 2 3 4 3 6 3 8 4 0 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 0 60 0 70 0 80 0 90 1 00 1 10 1 20 20 25 30 35 40 45 Outdoor inlet air D B C Low pressure at wide tube service valve MPa Indoor inlet air D B C 32 27 19 32 27 19 32 27 19 27 ...

Страница 28: ...ferred to AW735CL 3 2 3 7 4 2 4 7 5 2 5 7 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27 19 0 50 0 60 0 70 0 80 0 90 1 00 1 10 20 25 30 35 40 45 Outdoor inlet air D B C Low pressure at wide tube service valve MPa Indoor inlet air D B C 32 27 19 28 ...

Страница 29: ... to AW752CL 5 0 5 5 6 0 6 5 7 0 7 5 8 0 8 5 9 0 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 0 60 0 70 0 80 0 90 1 00 1 10 1 20 20 25 30 35 40 45 Outdoor inlet air D B C Low pressure at wide tube service valve MPa Indoor inlet air D B C 32 27 19 32 27 19 29 ...

Страница 30: ...referred to AW752CL 2 5 3 0 3 5 4 0 4 5 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 0 60 0 70 0 80 0 90 1 00 1 10 1 20 20 25 30 35 40 45 Outdoor inlet air D B C Low pressure at wide tube service valve MPa Indoor inlet air D B C 32 27 19 32 27 19 30 ...

Страница 31: ...ferred to AW764CL 3 0 3 5 4 0 4 5 5 0 5 5 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27 19 0 50 0 60 0 70 0 80 0 90 1 00 1 10 20 25 30 35 40 45 Outdoor inlet air D B C Low pressure at wide tube service valve MPa Indoor inlet air D B C 32 27 19 31 ...

Страница 32: ...ed to AS71CL 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27 19 0 50 0 60 0 70 0 80 0 90 1 00 1 10 20 25 30 35 40 45 Outdoor inlet air D B C Low pressure at wide tube service valve MPa Indoor inlet air D B C 32 27 19 32 ...

Страница 33: ...referred to AS100CL 6 0 6 5 7 0 7 5 8 0 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27 19 0 50 0 60 0 70 0 80 0 90 1 00 1 10 20 25 30 35 40 45 Outdoor inlet air D B C Low pressure at wide tube service valve MPa Indoor inlet air D B C 32 27 19 33 ...

Страница 34: ...125CL 7 0 7 5 8 0 8 5 9 0 9 5 10 0 10 5 11 0 11 5 12 0 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27 19 0 50 0 60 0 70 0 80 0 90 1 00 1 10 20 25 30 35 40 45 Outdoor inlet air D B C Low pressure at wide tube service valve MPa Indoor inlet air D B C 32 27 19 34 ...

Страница 35: ... 2 20 TC 3 11 2 93 2 84 2 70 2 54 2 34 CM 0 58 0 61 0 65 0 68 0 71 0 75 21 SHC 1 37 1 29 1 24 1 19 1 12 1 03 23 SHC 1 62 1 51 1 47 1 41 1 34 1 26 19 25 SHC 1 86 1 73 1 70 1 64 1 57 1 49 27 SHC 2 10 1 95 1 93 2 14 1 80 1 71 29 SHC 2 34 2 17 2 15 2 09 2 03 1 94 31 SHC 2 59 2 40 2 38 2 32 2 25 2 17 TC 3 27 3 11 3 01 2 86 2 69 2 48 CM 0 58 0 62 0 66 0 69 0 73 0 77 23 SHC 1 34 1 27 1 23 1 17 1 10 1 02 ...

Страница 36: ...3 91 3 70 3 57 3 40 3 19 2 94 CM 0 74 0 81 0 88 0 96 1 03 1 10 21 SHC 1 73 1 62 1 57 1 49 1 40 1 30 23 SHC 2 04 1 90 1 86 1 78 1 69 1 59 19 25 SHC 2 35 2 18 2 14 2 06 1 98 1 87 27 SHC 2 64 2 46 2 42 2 35 2 26 2 16 29 SHC 2 95 2 73 2 71 2 63 2 55 2 44 31 SHC 3 26 3 02 2 99 2 92 2 83 2 73 TC 4 11 3 92 3 78 3 61 3 39 3 12 CM 0 81 0 87 0 93 1 00 1 06 1 13 23 SHC 1 69 1 60 1 54 1 47 1 38 1 28 21 25 SHC...

Страница 37: ... 98 5 65 5 46 5 20 4 88 4 50 CM 1 05 1 18 1 31 1 44 1 57 1 71 21 SHC 2 64 2 48 2 40 2 28 2 15 1 99 23 SHC 3 11 2 91 2 84 2 72 2 59 2 43 19 25 SHC 3 59 3 33 3 27 3 15 3 03 2 86 27 SHC 4 04 3 76 3 71 3 80 3 46 3 30 29 SHC 4 51 4 18 4 14 4 02 3 90 3 73 31 SHC 4 99 4 62 4 58 4 47 4 33 4 17 TC 6 29 5 99 5 79 5 52 5 18 4 77 CM 1 20 1 31 1 42 1 53 1 64 1 75 23 SHC 2 58 2 44 2 36 2 25 2 11 1 96 21 25 SHC ...

Страница 38: ... 6 10 5 76 5 57 5 30 4 98 4 59 CM 0 95 1 13 1 31 1 49 1 67 1 85 21 SHC 2 69 2 52 2 44 2 33 2 19 2 03 23 SHC 3 17 2 97 2 89 2 78 2 64 2 48 19 25 SHC 3 66 3 40 3 33 3 21 3 09 2 92 27 SHC 4 12 3 84 3 78 3 90 3 53 3 36 29 SHC 4 60 4 26 4 22 4 10 3 98 3 80 31 SHC 5 08 4 71 4 67 4 55 4 41 4 25 TC 6 41 6 11 5 90 5 62 5 28 4 86 CM 1 22 1 36 1 49 1 63 1 76 1 90 23 SHC 2 63 2 49 2 41 2 29 2 15 1 99 21 25 SH...

Страница 39: ... 7 48 7 07 6 83 6 50 6 10 5 62 CM 1 24 1 44 1 65 1 85 2 05 2 26 21 SHC 3 30 3 09 3 00 2 85 2 68 2 49 23 SHC 3 89 3 64 3 55 3 41 3 24 3 04 19 25 SHC 4 49 4 17 4 08 3 94 3 79 3 58 27 SHC 5 05 4 71 4 63 4 75 4 32 4 13 29 SHC 5 64 5 23 5 17 5 03 4 88 4 66 31 SHC 6 23 5 78 5 72 5 58 5 41 5 21 TC 7 87 7 49 7 23 6 90 6 47 5 96 CM 1 53 1 68 1 84 2 00 2 16 2 31 23 SHC 3 23 3 06 2 95 2 81 2 64 2 44 21 25 SH...

Страница 40: ...8 97 8 48 8 19 7 80 7 33 6 75 CM 1 23 1 58 1 92 2 26 2 60 2 95 21 SHC 3 96 3 71 3 59 3 43 3 22 2 98 23 SHC 4 67 4 37 4 26 4 09 3 88 3 65 19 25 SHC 5 38 5 00 4 90 4 73 4 54 4 29 27 SHC 6 06 5 65 5 56 5 70 5 19 4 95 29 SHC 6 77 6 27 6 21 6 04 5 85 5 60 31 SHC 7 48 6 94 6 87 6 70 6 49 6 26 TC 9 44 8 99 8 68 8 27 7 77 7 16 CM 1 82 2 06 2 30 2 54 2 77 3 01 23 SHC 3 88 3 67 3 54 3 37 3 17 2 93 21 25 SHC...

Страница 41: ... 11 96 11 30 10 92 10 40 9 77 9 00 CM 2 15 2 37 2 59 2 80 3 02 3 23 21 SHC 5 28 4 95 4 79 4 57 4 30 3 98 23 SHC 6 23 5 82 5 67 5 45 5 18 4 86 19 25 SHC 7 18 6 67 6 53 6 31 6 06 5 72 27 SHC 8 08 7 53 7 42 7 95 6 92 6 60 29 SHC 9 03 8 37 8 27 8 05 7 80 7 46 31 SHC 9 97 9 25 9 16 8 93 8 66 8 34 TC 12 58 11 98 11 58 11 03 10 35 9 54 CM 2 36 2 55 2 74 2 93 3 13 3 32 23 SHC 5 17 4 89 4 73 4 50 4 23 3 91...

Страница 42: ... 11 46 TC 16 22 15 33 14 81 14 10 13 24 12 20 CM 2 81 3 37 3 94 4 50 5 07 5 63 21 SHC 7 16 6 71 6 50 6 19 5 82 5 39 23 SHC 8 44 7 89 7 69 7 39 7 02 6 59 19 25 SHC 9 73 9 04 8 86 8 55 8 21 7 76 27 SHC 10 95 10 21 10 05 10 60 9 38 8 95 29 SHC 12 24 11 34 11 22 10 91 10 58 10 12 31 SHC 13 52 12 54 12 41 12 11 11 74 11 31 TC 17 06 16 25 15 69 14 96 14 04 12 94 CM 3 68 4 10 4 51 4 93 5 35 5 77 23 SHC 7...

Страница 43: ...unning Amps A 0 13 0 28 5 09 5 50 Power input Kw 0 031 0 063 1 156 1 250 NOTE Data referred to indoor unit AW735CL model For other indoor unit models there could be some differences OUTDOOR UNIT AE752SCL COOLING Indoor Unit Complete Unit Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps A 0 37 0 41 6 32 7 10 Power input Kw 0 070 0 087 1 443 1 600 Full load conditions Run...

Страница 44: ... 3 93 5 00 Power input Kw 0 086 0 144 2 370 2 600 NOTE Data referred to indoor unit AW764CL model For other indoor unit models there could be some differences OUTDOOR UNIT AE71SCL3 COOLING Indoor Unit Complete Unit Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps A 0 77 0 67 3 66 5 10 Power input Kw 0 175 0 144 2 261 2 580 Full load conditions Running Amps A 0 77 0 67 4...

Страница 45: ...LING Indoor Unit Complete Unit Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps A 0 92 1 34 7 44 9 70 Power input Kw 0 210 0 29 4 502 5 000 Full load conditions Running Amps A 0 92 1 34 9 34 11 60 Power input Kw 0 210 0 29 5 902 6 400 NOTE Data referred to indoor unit AS125CL model For other indoor unit models there could be some differences Rating Conditions Indoor Air...

Страница 46: ...6 2 Electric Wiring Diagram AE726SCL AE735SCL AE752SCL 46 ...

Страница 47: ...AE752SCL3 AE764SCL3 47 ...

Страница 48: ...AE71SCL3 AE100SCL3 48 ...

Страница 49: ...AE125SCL3 49 ...

Страница 50: ...6 3 System Wiring Diagram AW726CL AW735CL AE726SCL AE735SCL AW752CL AE752SCL AW752CL AS71CL AE752SCL3 AE71SCL3 AW764CL AS100CL AE764SCL3 AE100SCL3 AS125CL AE125SCL3 50 ...

Страница 51: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima com ...

Отзывы: