6. TROUBLESHOOTING

6-1.  Check before and after troubleshooting

6-1-1.  Check power supply wiring.

Check that power supply wires are correctly connected to terminals and on the terminal plate in the indoor

unit.

6-1-2.  Check inter-unit wiring.

Check that inter-unit wiring is correctly connected to the outdoor unit from the indoor unit.

6-1-3.  Check power supply.

Check that voltage is in specified range (±10% of the rating).

Check that power is being supplied.

6-1-4.  Check lead wires and connectors in indoor and outdoor units.

Check that coating of lead wires is not damaged.

Check that lead wires and connectors are firmly connected.

Check that wiring is correct.

WARNING

Hazardous voltage can cause ELECTRIC SHOCK or

DEATH. Disconnect power or turn off circuit breaker

before you start checking or servicing.

5.

5-1.

5-1-1.

5-1-2.

5-1-3.

5-1-4.

5

-2. Air conditioner does not operate.

5

-2-1. Circuit breaker trips (or fuse blows).

A.  When the circuit breaker is set to ON, it trip

s immediately

. (Resetting is not possible.)

There is a possibility of ground fault.

Check insulation resistance.

If resistance value is 2M

or less, insulation is defective (“NO”).

NO

Measure insulation
resistance of electrical
parts in outdoor unit.

NO

Set circuit breaker to OFF.

*

Measure insulation
resistance of electrical
parts in indoor unit.

1

Remove inter-unit wires from 
terminal plate in outdoor unit.
Measure insulation resistance
of outdoor unit.

2

Remove inter-unit wires from 
terminal plate in indoor unit.
Then, pull the power plug out of 
the wall outlet
Measure insulation resistance
of indoor unit.

Insulation of 
outdoor unit 
is defective.

Insulation of 
indoor unit 
is defective.

WARNING

23

Содержание 387006131

Страница 1: ...TECHNICAL DATA SERVICE MANUAL INDOOR UNIT AD52AL AD64AL SPLIT SYSTEM AIR CONDITIONER AD64AL 0 8180 419 0 07 2005 387006132 Model No Product Code No AD52AL 387006131...

Страница 2: ...w wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line...

Страница 3: ...ions in Cool Dry Mode 16 4 7 Protections in Heat Mode 18 4 8 Sleep Function 21 4 9 Daily Timer 21 4 10 I FEEL Function 21 4 11 Drain Pump Operation 22 5 TROUBLESHOOTING 23 5 1 Check before and after t...

Страница 4: ...imensions Unit Height mm Width mm Depth mm Package dimensions Unit Height mm Width mm Depth mm Volume m3 Weight Unit Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE Power level measured at op...

Страница 5: ...mm Width mm Depth mm Package dimensions Unit Height mm Width mm Depth mm Volume m3 Weight Unit Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE Power level measured at operating conditions HI...

Страница 6: ...LK 9 BLK GRY 36 GRY VLT 18 VLT RED 18 BRN YEL 105 Safety devices Type Operating temp Open C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE...

Страница 7: ...Y VLT 18 VLT RED 18 BRN YEL 105 Safety devices Type Operating temp Open C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE Fan speeds H M L...

Страница 8: ...mistor Coil sensor TH1 Resistance Thermistor Room sensor TH2 Resistance Drain pump Model Rating Voltage Input Total head capacity Safety float switch Model Contact rating 10 5 10 3 PC 309564003 220 24...

Страница 9: ...9...

Страница 10: ...2 DIMENSIONAL DATA Units mm 10...

Страница 11: ...3 ELECTRICAL DATA 3 1 Electric Wiring Diagrams 11...

Страница 12: ...4 1 Cool Mode Operation 4 FUNCTION 12...

Страница 13: ...4 2 Heat Mode Operation 13...

Страница 14: ...4 3 Auto Cool Heat Mode Operation 14...

Страница 15: ...4 4 Dry Mode Operation 15...

Страница 16: ...4 5 Fan Mode Operation 4 6 Protection operations in Cool and Dry Mode 1 Indoor Coil Defrost Protection 5 Protection Operations in Cool and Dry Modes 16...

Страница 17: ...2 Outdoor Coil High Pressure Protection 17...

Страница 18: ...4 7 Protection Operations in Heat Mode 1 Outdoor Coil Deice Protection 18...

Страница 19: ...19...

Страница 20: ...2 Indoor Coil High Pressure Protection in Heat Mode 20...

Страница 21: ...4 8 Sleep Function 4 9 Daily Timer Function 4 10 IFEEL Function 21...

Страница 22: ...ogic 0 and 1 at the float switch pins connector respectively For the Fujitsu version of MCU the Overflow and Normal condition are indicated by a logic 1 and 0 at the float switch pins connector respec...

Страница 23: ...nect power or turn off circuit breaker before you start checking or servicing 5 5 1 5 1 1 5 1 2 5 1 3 5 1 4 5 2 Air conditioner does not operate 5 2 1 Circuit breaker trips or fuse blows A When the ci...

Страница 24: ...to ON Indoor PCB Ass y is defective NO Check power supply Power is being supplied to the indoor unit Circuit breaker is tripped Power failure Reset breaker Wait for recovery or contact power company R...

Страница 25: ...ary and secondary winding of transformer TR Indoor PCB Ass y is defective OK OK Measure resistance of indoor and outdoor fan motor winding FM Measure resistance of compressor motor winding CM OK Repla...

Страница 26: ...ature by temperature setting button button Outdoor unit still does not run Remote control unit is defective Try to run using another remote control unit COOL OK NO Is room temperature too high Try to...

Страница 27: ...tter in bearings Remove foreign matter or repair Repair or replace Measure resistance of outdoor fan motor winding Check fan motor capacitor Measure resistance of flap motor winding Fan cannot be turn...

Страница 28: ...otor winding is abnormally high Refrigerant gas shortage Charge refrigerant gas Measure power supply voltage Rotor may be locked up The voltage is too low 5 3 4 Compressor and outdoor fan do not run F...

Страница 29: ...emote control unit Receiver in lamp ass y may be defective may be defective Measure resistance of 4 way valve s winding COOL to HEAT Check voltage between Outdoor PCB ass y is defective terminals N an...

Страница 30: ...rtage YES Check position of remote control unit Cool or warm air from air conditioner reaches position directly Change position of remote control unit Wide and narrow tubes between indoor unit and out...

Страница 31: ...lampoon on the front side of the indoor unit will flash on and off when the thermistor is defective At the same time the outdoor unit will stop Indoor operate only for ventilation Temperature sensor...

Страница 32: ...sulation resistance tester and measure the resistance by placing a probe on each terminal screw on the terminal plate fig 2 Note that the ground line terminal should be skipped for the check 6 1 4 Mea...

Страница 33: ...then place a probe on the capacitor terminals as shown in fig 7 Observe the deflection of the pointer setting the resistance measuring range of the multimeter to the maximum value The capacitor is go...

Страница 34: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima it...

Отзывы: