User Guide
P225/EN FT/B11
MiCOM P225
Page 19/52
STATE OF THE PROTECTION FUNCTIONS (ACTIVE/INACTIVE) ACCORDING TO THE
OPERATION MODE OF THE MOTOR
The MiCOM P225 protection functions are automatically* activated or deactivated by the
relay itself according to the motor's operation mode (motor halted, start-up sequence, re-
acceleration phase or normal running condition). The table below indicates under which
conditions these protection functions are active or inactive.
Protective
functions
Motor halted
Start-up sequence Motor running
Re-acceleration
phase
Thermal image
Activated (Tr)**
Activated (Te2)** Activated
(Te1)** Activated
(Te2)**
Short-circuit Activated
Activated Activated Activated
Earth fault
Activated
Activated
Activated
Activated
Unbalance Activated Activated Activated
Activated
Excessive long start Deactivated
Activated
Deactivated
Activated
Stalled rotor whilst
running
Deactivated
Deactivated
Activated
Deactivated
Locked rotor at start Deactivated
Activated
Deactivated
Deactivated
Undervoltage
Deactivated
Activated**** Activated
Activated
Overvoltage Activated
Activated Activated Activated
Loss of load
Deactivated
Activated*** Activated*** Activated***
Overtemperature Activated
Activated Activated Activated
*
These protection functions are activated by the relay only if they have previously been
commissioned by the user.
**
The time constant used in the thermal model depends on the value of the motor load
current and on the motor's operating mode. The time constant indicated in brackets is
the one used by the relay.
***
The "loss of load" function is activated upon expiry of the Tinhib timer. This timer is
user settable, it is initiated by the relay when a motor start is detected.
****
The user can inhibit this function during the starting sequence.
4.10.1
The [49] THERMAL OVERLOAD submenu: Protection against thermal overload conditions
The MiCOM P225 relay produces a thermal image of the motor from the line current and the
negative component of the current consumed by the motor, in such a way as to take into
account the thermal effects created in the stator and in the rotor. The currents' harmonic
components contribute to the motor's heating. For this reason, the thermal replica uses the
line current
I
RMS
expressed in true rms value. The negative component currents consumed in
the stator generate in the rotor large amplitude currents which create a substantial
temperature rise in the rotor winding. The composition carried out by the MiCOM P225
results in an equivalent thermal current
I
eq
, the image of the temperature rise caused by the
current in the motor.
The current
I
eq
is calculated according to the following formula:
5
.
0
negative
RMS
eq
²)
I
Ke
²
I(
I
⋅
+
=
Starting from this equivalent thermal current, the thermal state of the motor
θ
is calculated
every cycle (every 20 ms for a 50Hz system) by the MiCOM P225 relay according to the
following formula:
)
/
t
(
)]
/
t
exp(
1
[
)²
I
/
I(
i
eq
1
i
Τ
−
⋅
θ
+
Τ
−
−
⋅
>
θ
=
θ
+
Содержание MiCOM P225
Страница 1: ...MiCOM P225 Motor Protection Relay Technical Guide P225 EN T B11...
Страница 2: ......
Страница 4: ...P225 EN T B11 Technical Guide Page 2 2 MiCOM P225 BLANK PAGE...
Страница 5: ...Connection Diagrams P225 EN CO B11 MiCOM P225 CONNECTION DIAGRAMS...
Страница 6: ......
Страница 8: ...P225 EN CO B11 Connection Diagrams Page 2 12 MiCOM P225 BLANK PAGE...
Страница 18: ...P225 EN CO B11 Connection Diagrams Page 12 12 MiCOM P225 BLANK PAGE...
Страница 19: ...Technical Specifications P225 EN TD B11 MiCOM P225 TECHNICAL SPECIFICATIONS...
Страница 20: ......
Страница 55: ...User Guide P225 EN FT B11 MiCOM P225 USER GUIDE...
Страница 56: ......
Страница 109: ...Menu of the HMI P225 EN HI B11 MiCOM P225 MENU OF THE HMI...
Страница 110: ......
Страница 158: ...P225 EN HI B11 Menu of the HMI Page 48 48 MiCOM P225 BLANK PAGE...
Страница 159: ...Maintenance P225 EN CM B11 MiCOM P225 MAINTENANCE...
Страница 160: ......
Страница 162: ...P225 EN CM B11 Maintenance Page 2 18 MiCOM P225 BLANK PAGE...
Страница 178: ...P225 EN CM B11 Maintenance Page 18 18 MiCOM P225 PAGE BLANCHE...
Страница 179: ...Communication P225 EN CT B11 MiCOM P225 COMMUNICATION...
Страница 180: ......
Страница 232: ...P225 EN CT B11 Communication Page 52 52 MiCOM P225 BLANK PAGE...
Страница 233: ...Setting P225 EN SV B11 MiCOM P225 SETTING...
Страница 234: ......
Страница 250: ...P225 EN SV B11 Setting Page 16 16 MiCOM P225 BLANK PAGE...
Страница 251: ...Installation Guide P225 EN IN B11 MiCOM P225 INSTALLATION GUIDE...
Страница 252: ......
Страница 254: ...P225 EN IN B11 Installation Guide Page 2 12 MiCOM P225 BLANK PAGE...
Страница 265: ...Test Report P225 EN RS B11 MiCOM P225 TEST REPORT...
Страница 266: ......
Страница 268: ...P225 EN RS B11 Test Report Page 2 20 MiCOM P225 BLANK PAGE...
Страница 287: ......